Heating Register List
One Heating has the following list of points. Some points may not be supported depending on the product.
Point
Description
1
On/Off
2
Lock
3
Setting Temperature Reference (Air/Water)
4
Set Hot Water Temperature
5
Alarm
6
HotWater On/Off
1
Operation Mode
2
Set Room Temperature
3
Hot Water Only Mode
4
Set PipeOut Water Temperature
5
Room Temperature
6
Error Code
7
Pipe Inlet Temperature Status
8
Water Tank Temperature Status
9
Solar Temperature Status
10
Pipe Outlet Temperature tatus
Function Code
Unit
Text-0
01/05
-
Stop (0)
01/05
-
Permit (0)
01
-
Air (0)
01
-
Normal (0)
01
-
Normal (0)
01/05
-
Stop (0)
03/06
-
-
03/06
03/06
03/06
03
03
-
03
03
03
03
Text-1
Text-2
Text-3
Start (1)
-
Prohibit (1)
-
Water (1)
-
Hot Water Only (1)
-
Abnormal (1)
-
Start (1)
-
Cool (1)
Heat (2)
Auto (3)
16 ℃ ~ 30 ℃ (60 ℉ ~ 86 ℉)
30 ℃ ~ 80 ℃ (86 ℉ ~ 176 ℉)
6 ℃ ~ 80 ℃ (42 ℉ ~ 176 ℉)
Please refer to LG error code list.
Text-4
Text-5
Text-6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-

Publicidad

loading