Fan Inverter
8

Alarm Flashlight

If an alarm flashlight is connected, see figure 11, the alarm flashlight will flash
briefly while Fan Inverter powers up, see figure 12. After the fan starts, there is
a delay and then the alarm flashlight flashes until the system pressure passes
the supervision level. The alarm flashlight can also flash during operation if the
system pressure drops below the supervision level. Write in the space below,
this Fan Inverter's supervision level:
________________(Pa) Supervision level
NOTE! If the alarm flashlight continues to flash for approximately 30 seconds
after Fan Inverter is started, or if it flashes continually during operation, there
is a problem, see Section '9 Troubleshooting'.
NOTE! If the alarm flashlight is connected to Fan Inverter, the alarm flashlight
does not flash if there is an input voltage interruption..
NOTE! To see if the alarm flashlight is functional, stop and restart Fan Inverter.