Operating Characteristics; Long Time Delay (L); Short Time Delay (S) - WEG ABWC Serie Instrucciones De Instalación, Operación Y Mantenimiento

Tabla de contenido

Publicidad

www.weg.net

11.2 OPERATING CHARACTERISTICS

11.2.1 Long time delay (L)

The overload protection function has a time delay characteristic that is inverse of the fault current.
1. Default current setting selector: Ir
0.1. Setting range in P and S types: (0,4-0,5-0,6-0,7-0,8-0,9-1,0)×In
0.2. Adjustable range in N and A types: (0,4~1,0)×In
- Iu: (0,5-0,6-0,7-0,8-0,9-1,0)×In
- Ir: (0,8-0,83-0,85-0,88-0,9-0,93-0,95-0,98-1,0)×Iu
2. Time delay setting selector: tr
- The default operating time is based on the time of 6 × Ir
- Adjustable range: 0,5-1-2-4-8-12-16-20s (8 modes)
3. Relay pickup current
- When the current exceeds (1.15) × Ir, the relay starts actuating.
4. The relay operates based on the largest load current between the R/S/T/N phases.

11.2.2 Short time delay (S)

The function for ground fault (overcurrent) protection has defined time characteristic and delay time in inverse
ratio of the fault current.
1. Default current setting selector: Isd
- Adjustable range: CAT.B, 1,5-2-3-4-5-6-8-10-Off×Ir;
CAT.A, 1,5-2-3-4-5-6-8-N/A-Off)×Ir.
2. Time delay setting selector: tsd
- The default operating time is based on the time of 10 × Ir;
- Inverse time (I2t On): 0,1-0,2-0,3-0,4s;
- Defined time (I2t Off): 0,05-0,1-0,2-0,3-0,4s.
3. The relay operates based on the largest load current between the R/S/T/N phases.
4. The relay can operate with instantaneous current through ZSI
5. Cat.A type should be set to Isd = Ir × 8 for short time; if the short time is set to
-Isd=Ir×10, it does not operate normally.
42 | ABWC Compact Air Circuit Breaker
Iu
Ir
tr
,9
,9
8
,8
1
,88
,93
4 12
.7
.85
,95
2
.6
.83
,98
1
Longa
1
,5
Tipo N e A
,5
duração ,8
Ir
tr
,8
8
,7 ,9
4
12
( S)
,6
1
2
.5
1
t
.4
.5
Curta
Ir
tr
I
Figure 11.1:
ZSC
Figure 11.2:
16
20
16
20

Publicidad

Tabla de contenido
loading

Tabla de contenido