Electrical Connections 
Modules  may  be  connected  in  series  and/or  parallel  to  achieve  the 
desired electrical output as long as certain conditions are met. Please 
use only the same type of modules in a combined source circuit.  
 
SunPower  recommends  that  all  wiring  be  double  insulated  with  a 
minimum rating of 85° C (185° F). All wiring should use flexible copper 
(Cu)  conductors.  The  minimum  size  should  be  determined  by  the 
applicable  codes.  We  recommend  a  size  not  less  than  4mm
insulation  type  should  be  appropriate  for  the  type  of  installation 
method  used  and  must  meet  SCII  (Safety  Class  II)  and  IEC  61730 
requirements. 
SunPower recommends a conservative minimum cable bend radius of 
equal  to  or  greater  than  40mm,  to  avoid  exposure  of  electrical 
connections to direct sunlight and not to place connector in location 
where water could easily accumulate. 
 
4.1 System & Equipment Grounding 
Please refer to the applicable regional and local codes on grounding 
PV  arrays  and  mounting  frames  for  specific  requirements  (e.g. 
lightning protection).  
 
Module Types 
SPR E, X , P series modules and our Maxeon and Performance Product Line 
are  compatible  with  Transformer  Less  (TL)  inverters,  when  used  as  an 
ungrounded PV source.  
No frame grounding requirements (including functional frame grounding), 
but may be subjected to local regulation. 
Functional system grounding of a polarity (positive or negative) is optional 
and may be subject to local requirements
E Series: 
SPR‐Eyy‐zz SPR‐Eyy‐zzz‐BLK SPR‐Eyy‐zzz‐COM 
X Series: 
SPR‐Xyy‐zzz SPR‐Xyy‐zzz‐BLK SPR‐Xyy‐zzz‐COM  
P Series/ Performance Product Line: 
SPR‐Pyy‐zzz‐COM  SPR‐Pyy‐zzz  SPR‐Pyy‐zzz‐BLK  SPR‐P3‐zzz‐COM 
SPR‐P3‐zzz SPR‐P3‐zzz‐BLK 
Maxeon Product Line: 
SPR‐MAX2‐zzz  SPR‐MAX2‐zzz‐COM  SPR‐MAX3‐zzz  SPR‐MAX3‐zzz‐
BLK SPR‐MAX3‐zzz‐COM 
 
Note:  If  you  are  installing  an  older  Module  Type  than  above 
mentioned, please refer to different/previous applicable Safety and 
Installation Manual. 
 
If  you  are  doing  a  frame  grounding  connection,  avoid  the  direct 
contact between Aluminum and Copper using an intermediate metal 
like steel or tin. 
 
4.2 Series Connection 
The modules may be wired in series to produce the desired voltage 
output.  Do  not  exceed  the  maximum  system  voltage  specified  in 
module datasheet. 
 
4.3 Parallel Connection 
The  modules  may  be  combined  in  parallel  to  produce  the  desired 
current output. Series string must be fused prior to combining with 
other  strings  if  the  resulting  maximum  reverse  current  exceeds  the 
fuse  rating  as  shown  in  the  datasheets.  Bypass  diodes  are  factory 
installed in the modules. Please refer to the applicable regional and 
local codes for additional fusing requirements and limitations on the 
maximum number of modules in parallel. 
©November 2019 SunPower Corporation. All rights reserved. Specifications included in this manual are subject to change without notice. 
2
.  The 
 
Safety and Installation Instructions ‐ Document 001‐15497 Rev S
5.0
Module Mounting   
The SunPower Limited Warranty for PV Modules is contingent upon 
modules  being  mounted  in  accordance  with  the  requirements 
described in this section. 
 
5.1 Site Considerations 
SunPower  modules  should  be  mounted  in  locations  that  meet  the 
following requirements:  
Operating Temperature: All SunPower modules must be mounted in 
environments that ensure SunPower modules will operate within the 
following maximum and minimum operating temperatures: 
Maximum Operating 
Temperature 
Minimum Operating 
Temperature 
Care  should  be  taken  to  provide  adequate  ventilation  behind  the 
modules, especially in hot environments. 
 
Design Strength:  SunPower modules are designed to meet a positive 
or  negative  (upward  and  downward,  e.g.  wind)  withstanding  test 
pressure load and a negative (or downward, e.g. static load or snow 
load)  withstanding  test  pressure  load,  as  per  IEC  61215,  when 
mounted in the configurations specified in Section 5.2 and Tables 1.2 
or 1.3 below.  
 
When mounting modules in snow prone or high wind environments, 
special care should be taken to mount the modules in a manner that 
provides  sufficient  design  strength  while  meeting  local  code 
requirements.  
 
Additional authorized Operating Environments:  
Modules  can  be  mounted  in  the  following  aggressive  environment 
according to the test limits mentioned below 
Salt mist corrosion testing: IEC 61701 Severity 6  
Ammonia Corrosion Resistance: IEC 62716 Concentration: 6,667ppm 
 
Excluded Operating Environments:  
Certain  operating  environments  are  not  recommended  for  specific 
SunPower  modules  and  are  excluded  from  the  SunPower  Limited 
Warranty for these modules. 
No SunPower module should be mounted at a site where it may be 
subject  to  direct  contact  with  salt  water,  or  other  aggressive 
environment. 
Modules  should  not  be  installed  near  flammable  liquids,  gases,  or 
locations with hazardous materials; or moving vehicules of any type. 
 
Performance Series Mounting Orientation 
Performance Series (P‐Series) modules are designed to be installed in 
landscape  orientation.  In  landscape  orientation,  P‐series  modules 
maintain higher power under row to row shading and edge soiling. 
 
5.2 Mounting Configurations 
 
Mounting  system  must  provide  a  flat  plane  for  the  modules  to  be 
mounted on and must not cause any twist or stress to be placed on 
the Module, even in case of thermal expension. 
 
Modules  may  be  mounted  at  any  angle  from  horizontal  to  vertical. 
Select  the  appropriate  orientation  to  maximize  sunlight  exposure.  
SunPower  recommends  for  a  good  performance  of  the  system 
(reduction of soiling effect) a minimum of 5˚ tilt angle. The cleaning  
frequency  must  be  increased  for  modules  installed  with  a  very  low 
angle. 
SUNPOWER CORPORATION 
+85 °C (+185 °F) 
‐40 °C (‐40 °F) 