1.
Turning the VF6 EX on: Momentarily press the detector
will beep once, vibrate once and the green LED will illuminate to indicate that the detec-
tor is on and ready for use.
2.
Turning the VF6 EX off: Momentarily press the
twice and vibrate twice and the green LED will turn off.
Turning the Sounder off and Vibrating motor off: Turn the VF6 EX on as described
3.
above. The VF6 EX will now operate with both the sounder and the vibrating motor. To
turn the sounder and vibrating motor off, press and hold the
green LED flashes. To turn the sounder and vibrating motor back on press and hold the
On/Off button until the green LED flashes, the sounder beeps and the unit vibrates.
Verify Operation: Before using VF6 EX, (1) Make sure the green LED is on, (2) Check
4.
VF6 EX on a known live AC voltage that is within the defined detection range of the VF6
EX.
Low Voltage Mode (12 to 1000V AC): ): Press and hold the 12 V button. The green
5.
LED will change to orange to indicate the VF6 EX is in the low voltage mode. While
pressing the 12 V button place the tip of the VF6 EX near an AC voltage. When AC volt-
age is detected the LED will turn red and flash, the sounder will beep and the detector
will vibrate. The flash, beeping and vibration rate will increase as the VF6 EX gets closer
to the voltage source. If the VF6 EX detects a medium voltage (100 V – 1000 V) it will
automatically change over to the medium voltage mode, the red LED will change to a
steady glow, the sounder will beep rapidly and the detector will vibrate constantly.
Operation
On/Off button.The VF5 will beep
On/Off button. The sounder
On/Off button until the