FUNCTIONAL SPECIFICATIONS
Insulation
Measurement range : 0.1 to 1000 MΩ
Short circuit current
* C.A 6513 only
The time required for the voltage present on the terminals to decrease by 90% of its value,
once the MΩ button is released (= discharge time), is 1s/µF.
Continuity
Measurement range : 0 to 10 Ω with reversal of the measurement current
Resistance (C.A 6513 only)
Measurement range : 0 to 1000 Ω
SPECIFICATIONS
Scale
0,1 MΩ to 1000 MΩ
Accuracy
± 5% of the measurement
Range
Empty voltage
Test current
R ≤ 500 kΩ
Scale
Accuracy
Short circuit
current
Empty voltage
Scale
Accuracy
Short circuit
current
Empty voltage
17
500 V
1000V*
600V
1200V
≥ 1 mA for
≥ 1 mA for
R ≤ 1 MΩ
≤ 6 mA
≤ 6 mA
0 - 10 Ω
± 3% of end of scale
≥ 200 mA
4.5 V ≤ V ≤ 6.5 V
0 - 1000 Ω
± 3% of end of scale
≥ 2mA
4.5 V ≤ V ≤ 6.5 V