Descargar Imprimir esta página

Johnson Controls P100 Serie Guia De Inicio Rapido página 6

Publicidad

6
Type number*
Short term overpressure
Burst pressure
Life at Rated Current
Temperature
Vibration
Range and differential
Setpoint tolerances
Approvals
Protection Class
Electrical Ratings
Electrical connections
Pressure connections
Quantity orders only
#
FLA = Full Load Amp
RLA = Resistance Load Amp.
LRA = Locked Rotor Amp.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions
beyond these specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable
for damages resulting from misapplication or misuse of its products.
Johnson Controls International, Inc.
Headquarters:
Milwaukee, WI, USA
European Headquarters:
Westendhof 8, 45143 Essen, Germany
European Factories:
Lomagna (Italy), Leeuwarden (The Netherlands) and Essen (Germany)
Branch Offices:
Principal European Cities.
This document is subject to change
Catalogue Section 6
S
pecifications
P100AA
standard duty;
P100CA
standard duty;
P100DA
standard duty;
P100AE
heavy duty;
P100CE
heavy duty;
P100EE
heavy duty;
Range 20 to 100 PSIG :
(1.4 to 6.9 bar)
Range 101 to 500 PSIG:
(6.9 to 34.5 bar)
Range 501 to 750 PSIG:
(34,5 to 52 bar)
3500 PSIG (241 bar)
Auto. reset models :
Man. reset models:
Ambient:
Refrigerant:
15 G max. (between 20 to 2000 Hz)
See pressure range tables
From ± 3 to ± 25 PSIG ( ± 0.2 to ± 1.7 bar)
See pressure range tables.
UL reg. file SA 516 Guide SDFY 2
CSA reg. file LR 63963 Class 1222-01
PED 97/23/EG category IV (TUV) DIN 32733
IP67 for models provided with wires; IP20 for models provided with QC
terminals
Standard duty : SPST
#
FLA 2.9 A, LRA 15 A at 240 Vac
Pilot duty 375 VA at 120/240 Vac
Max. 28 Vdc, 2 A
Heavy duty :
SPST
#
FLA 10 A, LRA 45 A at 240 Vac
Pilot duty 720 VA at 240 Vac
Max. 28 Vdc, 15 A
SPDT
#
NO: FLA 2.9 A, LRA 17.4 A at 240 Vac
Pilot duty 728 VA at 240 Vac
NC: FLA 10 A, LRA 45 A at 240 Vac
Pilot duty 720 VA at 240 Vac
Max. 28 Vdc, 15 A
1/4" quick connect terminals (6.35 x 0.81 mm) Auto. reset models only.
Cable 18 AWG ( 0.8 mm 2 ) stranded and tinned copper with 600V 105°C
PVC 1/16" insulation. Available for both Auto. Reset models and Man. Reset
models in lengths on request in multipliers of 6" (Standard length 48")
1/4" Female flare with valve depressor
1/4" ODM solder connection
6 mm ODM solder connection
Other connections available on request
SPST;
open low;
SPST;
open high;
SPST;
open high;
SPST;
open low;
SPST;
open high;
SPDT;
250 PSIG
(17.2 bar)
600 PSIG
(41.4 bar)
950 PSIG
(65 bar)
100.000 cycles
10.000 cycles
-30 to + 65 °C (Cable connection)
-40 to 135 °C (Quick connect terminals)
-55 to +135 °C
© 2003 Johnson Controls, Inc
P100
Issue 08/07/2003
auto. reset.
auto. reset.
man. reset.
auto. reset.
auto. reset.
auto. reset.
Printed in Europe
Order No. PD-P100-E