EN
Rectifying malfunctions
Fault
Pressing attachment can-
not be fully opened and
guided over the pressfit-
ting.
28
Cause
Roller drive is too
close to the pressing
attachment.
Action
1. Turn the handle anticlockwise until
the stop position is reached. The
hydraulic valve is opened.
2. Push the handle backwards.
3. Open the pressing attachment again
and place it correctly on the
pressfitting.
4. Push the handle forwards until the
roller drive makes contact with the
pressing attachment.
5. Turn the handle clockwise until the
stop position is reached. The
hydraulic valve is closed.