Wire Installation (Figure 3)
1.
Route wires go through wire hole in arm & pole.
Wire Connections (Figure 4 & 5)
1.
Connect supply wires to appropriate luminaire leads.
a.
Supply side ground wire to green luminaire lead.
b.
Supply side neutral wire to white luminaire lead.
c.
Supply side line voltage wire to black luminaire
lead.
2.
Only for use with 480V Wye systems. Per NEC, not for
use with ungrounded systems, impedance grounded
systems or corner grounded systems (commonly
known as Three Phase Three Wire Delta,Three Phase
High Leg Delta and Three Phase Corner Grounded Delta
systems). (Figure 5.)
Install wire junction cover plate (Figure 6)
1.
Install forked end of cover plate. Center tang hooks on
inside wall of arm. The rest of the cover plate should be
flush with the outside of the arm.
2.
Install #6 Philips screw through cover plate mounting
hole and tighten until head of screw is seated against
cover plate.
Neutral Wire
Line Voltage Wire
Ground Wire
Figure 4. Universal Voltage Single Phase System
White
Black
Green
Installation Instructions – LuxScape Arm
A
B
N
C
277 Volts
Figure 5. Wiring For 480V Wye Systems
Figure 6.
Cooper Lighting Solutions IB500008EN
480 Volts
480 Volts
277 Volts
480 Volts
277 Volts
Arm Cover Plate
Taptite Screw
Installation instructions