63.7
Over voltage protection indicator: (OVP)
The over voltage indicator indicates that the power inverter has shut itself down because its input voltage
exceeded the maximum input voltage.
63.8
Under voltage protection indicator: (UVP)
The under voltage indicator indicates that the power inverter has shut itself down because its input voltage fell
below minimum input voltage.
63.9
Over temp protection indicator: (OTP)
The over temp indicator indicates that the power inverter has shut itself down because its temp has become
overheated. The power inverter may overheat because it has been operated at power levels above its rating, or
because it has been installed in a location which does not allow it to dissipate heat properly. The power inverter
will automatically back up, once it has cooled off.
63.10 Overload protection indicator: (OLP)
The overload indicator indicates that the power inverter has shut down. A manual reset is necessary (switch it
OFF and ON again) to restart operation. This is a safety function to protect your battery when the inverter
operates in a remote area.
Model
HIPHOP pro 1500 12V
HIPHOP pro 2000 12V
HIPHOP pro 1500 24V
HIPHOP pro 2000 24V
HIPHOP pro 3000 24V
HIPHOP pro 1500 48V
HIPHOP pro 2000 48V
HIPHOP pro 3000 48V
DC
Input
over
DC
voltage shutdown
voltage alarm
16.0 VDC
15.5 VDC
32.0 VDC
31.0 VDC
62.0 VDC
61.0 VDC
Input
over
DC
Input
voltage alarm
10.5 VDC
21.0 VDC
43.0 VDC
43/85
under
DC
Input
under
voltage shutdown
10.0 VDC
20.0 VDC
42.0 VDC
V 1.0