Trip Curve
Courbe de déclenchement
Auslösekurve
Curva del disparo
Class 10
1000
100
10
1
0.1
1
Multiple of FLA
Intensités pleine charge multiples
Short Circuit Ratings
Table 1 Standard Fault Short Circuit Ratings per UL508 and CSA 22.2 No. 14
E1 Plus Cat. No.
Max. available fault
current (kA)
ED1CP, ED1DP, ED1EP,
193,193S
EECP, EEDP, EEEP, EEPP,
5
EERP, EESP
Table 3 Short Circuit Ratings per EN 60947-4-1
E1 Plus Cat. No.
Prospective S.C.
current, Ir (kA)
ED1CP, ED1DP, EECP,
1
EEDP, EEPP, EERP
193, 193S
ED1EP, EEEP, EESP
3
Type 2 Fuse Selection Table for Class gG and Class aM Fuses
at Line Voltage of 400V, 50Hz
Motor
Fuse
Contactor
Rated
Type gG
Type aM
Opera onal
Rated
Rated
Catalog
Current
Current
Number
Current I
e
1)
2)
[kW]
[A]
[A]
[A]
0.37
1.1
4
2
100-C09... 193-EECP
0.55
1.5
4
2
100-C09... 193-EECP
0.75
1.9
6
4
100-C09... 193-EECP
1.1
2.7
6
4
100-C09... 193-EECP
1.5
3.6
6
4
100-C09... 193-EECP
2.2
4.9
10
6
100-C09... 193-EEDP
3
6.5
16
10
100-C09... 193-EEDP
4
8.5
20
10
100-C09... 193-EEDP
5.5
11.5
25
16
100-C12... 193-EEDP
7.5
15.5
32
16
100-C16... 193-EEDP
Recommended fuse sizes based on the following starting conditions:
≤ 3 kW Starting current max. 6 x Motor rated current, Starting time max. 5 s
> 3 kW Starting current max. 7 x Motor rated current, Starting time max. 5 s
1)
Typical motor currents according IEC 60947-4-1 Table G.1
2)
Incomplete catalog number, add coil and auxiliary contact codes
3)
Overload relay 193-ED... with the same current setting range may also be used (up to 45A)
42053-028-01
DIR 42053-028 (Version 03)
Curva de disparo
Curva di intervento
Class 15
1000
100
10
1
0.1
8
1
Múltiplo de FLA
Vielfache des FLA-Wertes
COLD START
DEMARRAGE A FROID
KALTSTART
ARRANQUE EN FRIO
PARTIDA À FRIO
AVVIAMENTO A FREDDO
Table 2 Type I and Type II Fuse Coordination with Bul. 100-C contactors per EN 60947-4-1
Max. voltage (V)
S.C.P.D.
Not resticted to
600
fusing only
193
Conditional S.C.
Max. voltage (V)
S.C.P.D.
current, Iq (kA)
Not resticted to
100
690
fusing only
O/L Relay 193-EE..
S.C. Current
Current
Catalog
Setting
Iq
Number
Range
3)
[A]
[kA]
1.0 - 5.0
1.0 - 5.0
1.0 - 5.0
1.0 - 5.0
1.0 - 5.0
50
3.2 - 16
3.2 - 16
3.2 - 16
3.2 - 16
3.2 - 16
Class 20
1000
100
10
1
0.1
8
1
Intensités pleine charge multiples
Multiplo di Max amp.
HOT START
DEMARRAGE A CHAUD
WARMSTART
ARRANQUE EN CALIENTE
PARTIDA À QUENTE
AVVIAMENTO A CALDO
E1 Plus Cat. No.
Contactor Cat. No. Max. starter FLC
100-C09
ED1CP, ED1DP, EECP,
100-C12
EEDP
100-C16
100-C23
100-C09
100-C12
ED1EP, EEEP
100-C16
100-C23
Table 4 High Fault Short Circuit Ratings per UL508 and CSA 22.2 No. 14
E1 Plus Cat. No.
ED1CP, ED1DP, ED1EP,
193
EECP, EEDP, EEEP
(5)
1000
100
10
1
0.1
8
1
Prospective S.C.
Conditional S.C.
Max. voltage
(A)
current, Ir (kA)
current, Iq (kA)
(V)
9
12
1
16
23
100
600
9
12
3
16
23
Max. starter FLC
Max.available
Contactor Cat. No.
fault current (kA) Max. voltage (V)
(A)
100-C09
9
100-C12
12
100
100-C16
16
100-C23
23
Class 30
8
Type I Max. Class
Type II Max. Class
J or CC fuse (A)
J or CC fuse (A)
20
15
20
20
30
30
40
40
20
15
20
20
30
30
40
40
Max. UL Class J or CC
fuse, CSA HRCI-J (A)
20
20
600
30
40