INSTALLATION INSTRUCTIONS
DEHNguard DG TT 2P 5 275, DG TT 5 275
1,2 Nm
Cruciform drive
(e.g.Pozidriv ® Z2)
There is no distance from the
SPD to any earthed conductive
surface required. /
Es ist kein zusätzlicher Abstand
vom SPD zu geerdeten Flächen
(indoor use only / Nur im Innenraum)
einzuhalten.
TT / TN
DG TT 2P 5 275
PE
S3
PE
L N
S2
F2
F1
L
L'
N
N'
Coordination / Koordination
LPZ 0
LPZ 1
LPZ 2
A
DEHNguard
DG TT 2P 5 275,
DG TT 5 275
Class I
Class II
Class III
Type 1
Type 2
Type 3
Type 2
EN 61643-11: ...
Class II
IEC 61643-11: ...
TT / TN-S DG TT 5 275
PE
S3
PE
L1 L2 L3 N
F2
F1
L1
L2
L3
N
Fault indication / Defektanzeige
DIN VDE 0185-4: ...
LPZ 3
IEC 62305-4: ...
Technical data / Technische Daten
type
DG TT 2P 5 275
U
230 V (50/60 Hz)
N
U
275 V (50/60 Hz)
C
U
255 V (50/60 Hz)
C [N-PE]
max.
MCB C 63 A
I
6 kA
SCCR
I
(N-PE)
100 A
fi
I
(L-N)
15 kA
max (8/20)
I
(N-PE)
40 kA
max (8/20)
ϑ° C
-40°C ... + 80°C
humidity / Feuchte
5% ... 95%
I
< 5 μA
PE
Ports
1
IP-Code
IP 20 (built in /eingebaut)
L x W x H
85 mm x 18 mm x 65 mm
S2
L1'
L2'
L3'
N'
DG TT 2P 5 275
DG TT 5 275
green
ok
replace
red
DG TT 2P 5 275
green
DG TT 5 275
Publication No. 1869 UPDATE 11.13 Id. No. 068130
DG TT 5 275
230/400 V (50/60 Hz)
□
min.
L, N,PE
□
max.
L, N,PE
85 mm x 36 mm x 65 mm
Backup fuse / Vorsicherung
DEHNguard
DG TT 2P 5 275 , DG TT 5 275
F1 ≤ MCB C 63 A
F1
F2
F1 > MCB C 63 A
F2
F2 ≤ MCB C 63 A
Fuse F1
S
/ mm²
S
/ mm²
2
3
A
25
4
6
35
4
6
40
4
6
50
6
6
63
10
10
>63
10
10
© COPYRIGHT 2013 DEHN + SÖHNE
11 mm
11 mm
0,75 mm²
6 mm²
10 mm²
Fuse F2
A
---
---
---
---
---
63
p.t.o.
Safety
Instructions