Connect the power and the load into the connection-wire
column of the sensor according to connection-wire diagram.
➢
The sensor aimed at the mouth of bottom-stand and turned
anti-clockwise.
CONNECTION-WIRE DIAGRAM:
(See the right figure)
TEST:
➢
Turn the TIME knob to minimum (-) position with
anti-clockwise. Turn the LUX knob to SUN position
with anti-clockwise.
➢
Switch on the power, the controlled load and
indication lamp both are not working. Preheat 30
sec later, the load and indication lamp should be
turned on synchronization. In the absence of no
inductor signals, the load should be stopped working within 5-30sec, the indicator lamp is
turned off.
➢
After the first sense is finished, and it will sense again after 5~10sec. The load should work.
When there is no inductor signals in the indicator lamp, the load should be stopped working
within 5-15sec.
➢
Turn LUX knob clockwise on the minimum (MOON position). If it is adjusted in the less than
10LUX, the inductor load should not work after load stop working. If you cover the detection
window with the opaque objects (towel etc), the load works under no induction signal
condition, the load should stop working within 5-15sec.
Note: when testing in daylight, please turn LUX knob to
position, otherwise the sensor lamp could not work!
NOTES:
➢
Electrician or experienced human can install it.
➢
The unrest objects can't be regarded the installation basis-face.
➢
In front of the detection window there aren't hinder or unrest objects effecting detection.
➢
Avoid installing it near air temperature alteration zones for example: air condition, central
heating, etc.
➢
Please don't open the case for your safety if you find the hitch after installation.
➢
If there are some difference between instruction and the function the product has, please
give priority to product and sorry not to inform you additionally.
SOME PROBLEM AND SOLVED WAY
➢
The load doesn't work:
a. Check the power and the load.
b. Whether the indicator light is turned on after sensing? If yes, please check load.
c. If the indicator light does not turn on after sensing, please check if the working light
corresponds to the ambient light.
d. Please check if the working voltage corresponds to the power source.
➢
The sensitivity is poor:
a. Please check if in front of the detection window there are hinder that effect to
receive the signals.
b. Please check the ambient temperature.
c. Please check if the signals source is in the detection fields.
d. Please check the installation height.
➢
The sensor can't shut automatically the load:
a. If there are continual signals in the detection fields.
b. If the time delay is set to the longest.
c. If the power corresponds to the instruction.
d. If the air temperature change near the sensor, air condition or central heating etc.
(SUN)