Descargar Imprimir esta página

Hubbell AFB10G55 Instrucciones De Instalación página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

Box Installation shown: (see Figure 3) — (sub-floor shown)
1. Cut opening in floor as shown for box.
2. Install box with temporary cover.
3. Secure box to floor using four #8 flat head screws
(not provided).
After Box installation: (see figure 5 and 6)
4. Remove and retain four #8-32 flat head screws [1] from top four corners of
the box.
5. Remove top mounting flange [2] with temporary cover [3] from box.
6. Turn two #10 screws [4] clockwise. Tighten screws until pawl arm is secured
to underside of floor. (see Figure 4)
7. Install conduits runs as required.
8. Re-install top mounting flange [2] with temporary cover [3]. (See figure 6,
Ensure that top mounting flange [2] align with notches [5] in box.)
CAUTION: Temporary covers are intended to keep debris from entering box
after installation and are not intended to support loads. Replace with perma-
nent flange/cover immediately after installation or temporarily reinstall metal
cover [3].
9. Consult electrical device mounting plate installation instructions for wiring de-
vice installation. Use Blank Plate FB10MPBNK where no device is installed.
10. Attach Flange with Cover (see figure 7).
Figure 5
PD2614
(Page 2)
08/14
PRINTED IN USA
Figure 3
11.0" max.
[27.9 cm]
11-1/2"
[29,2 cm]
Figure 4
3/4" floor shown
Pawl arm
Pawl arm adjustment for floor
thicknesses from 3/4'' [19.0 mm]
to 2.00" [51 mm] max.
3
Figure 6
4
1
2
5
Carpet Installation shown
Cut opening in carpet as shown for AFB Flange.
See Fig. A - For installation of AFB Flange with Cover detail.
#8 screws
10-1/2"
[26.7 cm]
AFB Flange for Carpet Installation – SURFACE (shown) - Open Cover and turn Jack Screws [4] to adjust AFB Flange
with Cover flush to surface of carpet.
Figure A
Carpet Flooring
Box
Floor Box
Depth
AFB10G55, xxCHI
5-1/2"
10GAFBCVRxx or 10GAFBCVRxxC
AFB Flange for Tile Installation – SURFACE (shown) - Open Cover and turn Jack Screws[4] to adjust AFB Flange with
Cover flush to surface of Tile.
Figure B
2
Access Flooring
Box
Floor Box
Depth
AFB10G55, xxCHI
5-1/2"
10GAFBCVRxx or 10GAFBCVRxxC
5
PD2614
(Page 3)
08/14
9.0"
[22,9 cm]
Apply Silicone
To attach Flange,
See Fig. 7.
Carpet
AFB Flange With Cover
Floor
Optionally: Apply
silicone compound.
AFB Flange With Cover
Tile
PRINTED IN USA
compound to
flange.
Cover
Jack
Screws
Apply gasket
Jack
Screws
Mounting flange on box

Publicidad

loading

Este manual también es adecuado para:

Afb10g55chi