19 Reset

ATTENTION: Ther is no longer any protection by
switching off the load after the reset. Teach the door
operator in again before re-commissioning. For this carry out
Teaching in the door operator (Chapter 15) .
Reset (saved values of the teach-in runs)
During one of the 3 status messages A, B or C (see Chapter
10) press the pushbuttons
for longer than 8 seconds and less than 10 seconds. The
indicator lamp flashes (r), then the status message is
displayed; the reset is carried out.
The remote transmitters are not deleted.
Reset, factory setting
• Pull out the plug (1).
• During one of the 3 status messages A, B or C (see 10)
press the pushbuttons
longer than 12 seconds. The indicator lamp flashes slowly
at first, then quicker (rES). Then the status display
reappears, the reset is made.
The values shown under Programming (Chapter 18) are
set. The remote transmitters are not reset.

20 Attaching additional safety devices

Photo cell

Function: When the safety input is activated (opening the
contact) the operator stops and reverses as far as the OPEN
end position.
If the "automatic closure" function is also activated, following
the third successive obstruction message, the operator will
move to the OPEN end position and shut down.
Connection: Pull out plug with yellow bridge on the external
junction 2 and store it. Plug on safety device.
Safety rail, opto-sensor
connected by extension modules.

EMERGENCY stop

Function: If the external safety device is operated when the
door is moving (Contact opened), the door stops immediately.
Once the EMERGENCY stop contact has closed, the door
operator can be moved again with the next pulse.
Connection: Pull out plug with green bridge on the external
junction 5 and store it. Plug on safety device.

21 Additional connections

Additional lighting

Connection must be performed only by qualified electricians.
In addition to the operator light (40W), optional lighting of a
maximum of 60 W (no tubular fluorescent lamps) can be
connected to terminals 1 and 2.
Note: Some energy saving lamps can interfere with the radio
signal.

External pulse input

An external pulse signal (e.g. wall button) can be connected
to terminals 18 and 19.

Additional antenna

An external antenna can be connected to terminals 21 and 20
(GND). The internal antenna (terminal 21) must be
disconnected.
12 / 208
and Menu
simultaneously
and Menu
simultaneously for
warning light
and
20
21
Figure: Control board See also page 164.

22 Troubleshooting

Interference frequencies
The wireless signals of other 433 MHz transmitters can
interfere with the door operator.
Self-test
The system runs a self-test after initialisation, after each
motor operation and after every 2.25 hours in idle mode.
Error free = status message.
Error messages*
2
EEprom data
3
Current measurement
4
Hardware Photo cell
5
Switch off thyristors
6
Switch off relay
7
Watchdog test
8
ROM test
9
RAM test
Troubleshooting: Reset (Chapter 19) and then perform work
step Teaching in the door operator (Chapter 15)
If the error occurs again, request customer service.
are
Note: If the same error occurs in two successive self-tests,
the control system will be disabled (commands are rejected).
After approximately one further minute, the system runs
another self-test. If no errors are detected, the control system
is enabled again. If the error persists, a reset will need to be
performed. This will delete all settings and the door operator
will have to be taught in again.

Causes of errors/Remedies

Description
Door operator light
flashes evenly
Door operator light
flashes at intervals of
4
Entrapment
protection device not
working.
The operator is not
working at all.
The operator is
defective.
N000924 12/2010
19
18
Possible cause/Remedy
The door has hit an obstruction, do
function test
Door operator is not taught in,
attention no protection by load
switch-off! Carry out door operator
Teaching in the door operator
(Chapter 15)
Incorrect setting of door or
entrapment protection device /
Reset and teach in again
None or wrong voltage supply / The
fuse of the motor control is defective
/ Check external terminals 7 and 8.
The slides are not snapped-in
properly./The toothed belts are not
tensioned correctly./The door
thresholds are frozen.
2
1
Magic 600