10 – Display and Configuration
1
10-5-3 Battery Setup
Enter the UPS system setup menu. Use the scroll buttons ( , )
1
2
to move the cursor to "BATTERY SETUP", then press the enter
button (
).
At UPS startup, you must enter information about the battery,
including amp hour rating, number of strings and charger current.
Use the following formulas as a guide.
3
TYPE (AH) – Internal batteries are 9 AH per string. The AH
rating for external batteries is equal to the number after the "V"
in the model name. For example, BP480V26B = 26 AH. When
internal and external batteries are used, total the values of each
4
battery string. For example, SU40KX and BP480V26B = 58 AH
(9+9+40).
BAT STRINGS – If only internal batteries are used, enter the
number of strings. For example, SU40KX has two internal battery
strings, so enter "2". If both internal and external batteries are
5
used, do not count the internal battery. For example, SU40KX with
BP480V55, enter "1".
CHARGER CURRENT – See
about setting the charger current.
6
2
From the "EXT BAT TYPE" screen, use the scroll buttons ( ,
) to select the desired settings and press the enter button (
to confirm the settings. Note: See step 1 for additional guidance
on AH settings.
7
BP480V26B = 26 AH
BP480V40C = 40 AH
BP480V55 = 55 AH
BP480V78 = 78 AH
8
BP480V103 = 103 AH
BP480V140 = 140 AH
9
10
Battery Strings
3
Use " " or " " to select the desired number of battery strings,
then press "
" to confirm. Note: See step 1 for information
about battery string settings.