Installation and operating instructions Wilo-Control EC/ECe-Booster
Commissioning
1. Press the operating button for 3 s.
⇒ Menu 1.00 appears.
2. Turn the operating button until menu 3.00 appears
3. Press the operating button.
⇒ Menu 3.01 appears.
4. Press the operating button.
5. Change value to "on".
6. Press the operating button.
⇒ Value saved, pump enabled.
▶ Automatic mode switched on.
Make sure the following points are observed during operation:
▪ Keep the switchgear closed and secure it against unauthorised opening.
▪ Switchgear attached in an overflow-proof manner (protection class IP54).
▪ Not exposed to direct sunlight.
▪ Ambient temperature: 0 ... 40 °C.
The following items of information are shown on the main screen:
▪ Pump status:
– Number of registered pumps
– Pump activated/deactivated
– Pump On/Off
▪ Operation with standby pump
▪ Control mode
▪ Actual pressure value
▪ Active field bus operation
Furthermore, the following information is available via menu 4:
1. Press the operating button for 3 s.
⇒ Menu 1.00 appears.
2. Turn the operating button until menu 4 appears.
3. Press the operating button.
▶ Menu 4.xx appears.
Actual pressure value in bar
Switchgear running time
The time will be displayed in minutes (min), hours (h) or days (d) de-
pending on the unit.
Running time: Pump 1
The time is stated in minutes (min), hours (h) or days (d) depending
on the unit. The display varies depending on the timespan:
▪ 1 hour: Display in 0 ... 59 minutes, unit: min
▪ 2 hours to 24 hours: Display in hours and minutes separated by a
decimal point, e.g. 10.59, unit: h
▪ 2 days to 999 days: Display in days and hours separated by a decimal
point, e.g. 123.7, unit: d
▪ From 1000 days: Display in days, unit: d
Running time: Pump 2
The time is stated in minutes (min), hours (h) or days (d) depending
on the unit.
Running time: Pump 3
The time is stated in minutes (min), hours (h) or days (d) depending
on the unit.
Switchgear switching cycles