❒ When wiring to additional standard
fixture only: Strip the motion sensor's
red wire and connect to the standard
light's black wire. Connect all white wires
together. Total fixture ratings must not
exceed 360W (3.0 A.).
NOTE: All wiring between fixtures should be
run in accordance with the National Elec-
trical Code (Canadian Electrical Code in
Canada) through conduit or another ac-
ceptable means. Contact a qualified
electrician if there is any question as
to the suitability of the system.
BLACK
WHITE
Wiring to Motion Light &
Standard Fixture
COMPLETE THE
INSTALLATION
❒ Stuff the wires into the junction box.
Make sure none of the wires get pinched.
❒ Install one 100 W max. light bulb.
❒ Install the fixture top. Secure with
decorative screws.
❒ Caulk fixture mounting surface with
silicone weather sealant. You may want
to wait until you have completed the
tests and adjustments on page 4.
598-1041-04
OPTIONAL WIRING
RED to
BLACK
(Standard)
3
❒ This fixture is provided with a sensor
rated for 360 W. Since the fixture is only
rated 100 W, 260 W of additional load
may be controlled by this sensor.
❒ When determining what a fixture is rated
for, do not simply look at the rating on the
lamp in the fixture. Look at the marking
which specifies the maximum lamp watt-
age for which the fixture is suitable.
❒ Once you have selected the fixtures to
be connected and determined their
maximum ratings, add these ratings up.
For instance, if you have 3 fixtures
rated 100 W, 150 W, and 75 W respec-
tively, you have a total load of 325 W.
Master
BLACK
Wiring to Control One Motion Sensing
Lantern (Slave) from Another (Master)
Slide the fixture onto
the mounting screws
and tighten nuts.
Slave
RED
BLACK
WHITE
Junction
Box