Technical parameters

Supply terminals:
Voltage range:
Burden (unloaded):
Max. dissipated power:
Supply voltage tolerance:
Supply indication:
Control
Button - control. terminals:
Control voltage:
Power the control input:
Impulse length:
Glow tubes connection
(terminals: A1 - T):
Max. amount of glow lamps
connected to controlling
input:
Blocking input - terminals:
Control. voltage:
Power input:
Glow tubes connetions
(terminals A1 - B):
Impulse length:
Output
Output status indication:
Load capacity:*
Other information
Operating temperature:
Storage temperature:
Operating position:
Mounting:
Protection degree:
Overvoltage category:
Pollution degree:
Max. cable size (mm
2
):
Dimensions:
Weight:
* Due to a large number of light source types, the maximum load depends on the inter-
nal construction of dimmable LEDs and ESL bulbs and their power factor cos φ. The
power factor of dimmable LEDs and ESL bulbs ranges from cos φ = 0.95 to 0.4. An ap-
proximate value of maximum load may be obtained by multiplying the load capacity
of the dimmer by the power factor of the connected light source.
- list of tested light sources can be found here: www.elkoep.com/solutions/
Photosensor SKS
Sensor is external and is connected to terminals IN.
Sensor is installable to panel (by screw-able transparent cover) to opening with diameter
16 mm. A part of the sensor is a plastic holder for placing into the wall or to another place.
Length of a line connector to the sensor cannot be more than 50 m (164´). Doublecure
cable can be used as wire diameter min. 2x 0.35 mm
degree is IP44.
It is possible to use photoresistor, which changes resistance in accordance with ambient
illumination, as a sensor. Tolerance sensor ± 33 %.
Installation ans setup of photosensor:
- sensor has to be mounted vertically over working area where is the constant value of
lighting
- sensor can not be installed nearby the windows (min. 2 m / 6.6´) and shouldn't be ex-
posed to direct sunlight (neither artifi cial light)
- setting of desired level of illumination shoud be performed at a maximum darkness (e.g.
shutters down) to exclude infl uence of any illumination from the outside
LIC-1
A1 - A2
AC 230 V / 50 - 60 Hz
max. 1.6 VA / 0.8 W
1 W
±15 %
green LED
A1 - T
AC 230 V
max. 0.6 VA
min. 80 ms / max. unlimited
Yes
max. amount 50 pcs
(measured with glow lamp 0.68 mA / 230 V AC)
A1 - B
AC 230 V
max. 0.1 VA
No
min. 80 ms / max. unlimited
2x MOSFET
red LED
300 W (at cos φ =1)
-20 °C to 35 °C (-4 °F to 95 °F)
-20 °C to 60 °C (-4 °F to 140 °F)
any
DIN rail EN 60715
IP40 from front panel / IP10 terminals
III.
2
solid wire max. 2x 2.5 or 1x 4 /
with sleeve max. 1x 2.5 or 2x 1.5 (AWG 12)
90 x 17.6 x 64 mm (3.5˝ x 0.7˝ x 2.5˝)
66 g (2.33 oz.)
2
and max. 2x 2.5 mm
Function
Un
T
B
max.
reg.
LED
LED Un
T-button control:
- pressing button shortly (< 0.5 s) always turns of lamp
- pressing button longer (0.5.. 3 s) turns on lamp in automatic regulation mode
- pressing button long (> 3 s) turns on lamp to full illumination - „cleaner" mode
- after turning on the power supply, the dimmer is always turned off
Thyristor B:
Serves to block automatic regulation (lamp turns off ).
WARNING! The lamp may be turned on in "cleaner" mode even while blocked.
After ending block mode, the lamp remains off .
Control elements on the instrument panel:
- load switch - has 2 positions for each type of load that diff er in their regulation curves
(sets the best position for the connected load)
- the lamp turns off (if previously on) whenever the switch settings are changed
- potentiometer setting of minimal luminance
- potentiometer setting of desired lighting level during automatic regulation
- the potentiometer status is stored in short-term memory whenever a change occurs - a
green LED fl ashes (approx. 3s) while storing
- both lighting levels are storing in EEPROM memory during a power supply failure - LED
meanwhile briefl y turns off
WARNING!
- both lighting levels must be reset when switching load type
- both lighting levels may only be set in automatic mode while the lamp is on
- potentiometer setting of lighting level fade speed - only available in automatic regula-
tion mode
- determines the reaction time to changes in surrounding lighting level
LED indicators:
green LED:
- illuminates, if supply voltage is present
- fl ashes when storing set luminance values
- shortly turns off when power failure occurs - stores settings
red LED:
- illuminates during active output (at arbitrary luminance level)
- fl ashes slowly when operating temperatures exceeded, output is simultaneously dis-
connected
- fl ashes quickly when overvoltage protection is activated (approx. 1 minute); output is
simultaneously disconnected
Warning
Device is constructed for connection in 1-phase main AC and must be installed according
to norms valid in the state of application. Connection must be realized according to the
details in this instruction manual. Installation, connection, setting and operating should
be made by qualifi ed electrician staff only, who has learnt these instruction and functions
2
. Protection
of the device. This device contains protection against overvoltage peaks and disturbancies
in supply. For correct function of the protection of this device there must be a suitable
protections of higher degree (A, B, C) installed in front of them. Before installation the main
switch must be in position "OFF" and the device should be de-energized. Don´t install the
device to sources of excessive electro-magnetic interference. By correct installation ensure
ideal air circulation so in case of permanent operation and higher ambient temperature
the maximal operating temperature of the device is not exceeded. For installation and
setting use screw-driver cca 2 mm (0.1˝). The device is fully-electronic - installation should
be carried out according to this fact. Non-problematic function depends also on the way
of transportation, storing and handling. In case of any signs of destruction, deformation,
non-function or missing part, don´t install and claim at your seller. After the product ex-
ceeds lifetime, it should be removed and placed in protected dump.
Important instructions and cautions - dimmer is not designated for controlling of motors.
HDO warning signals and other similar signals spreaded by main, can cause interruption of
dimmer. Interruption is active only during transmitting of these signals.
2 / 2
0.5s - 3s
>3s
3s
t
t
<0.5s