Setup
Be sure to turn the power OFF for setting.
1
Only when using this adaptor more than one
set the address setting switch (SW001).
Avoid duplication referring to the combination table below.
• The system address is registered as 31.
• If the Interface Adaptor is present in the system, do not
allow the address to duplicate with the Interface Adaptor.
Switch No.
1 2 3 4 5 6
1
2
3
4
5
6
7
8
9
10
1 1
12
13
14
15
16
● : ON - : OFF
2
Set the function setting switch (SW002).
z [SW1] Switching the setting method for the central address.
OFF*: Sets using the central control device.
ON : Sets using the address setting switch of this adaptor.
(Adaptor address set in step 1 is central control address)
When setting the SW1 to ON:
• The central address is shared with the adaptor address.
• The central address is fixed by the address switch.
z [SW2] Switching the prohibition method for the remote control switch
OFF: Remote control operation is prohibited.
ON*: Remote control operation is permitted, and then operation is cancelled.
z [SW3] Recovery from power failure
OFF*: - (Depends on the room air conditioner setting.)
ON: Recovers in the state before power failure.
z [SW4] Not in use (For function enhancement)
z [SW5/6] Switching the contact input signal (table below)
Status
SW5 SW6
OFF* OFF*
OFF ON
26
(EN)
Switch No.
1 2 3 4 5 6
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Contact input
External equipment
details
operation details
Input 1:
Short circuit : Start
Start/stop signal
Open circuit: Stop
(Static)
Input 2:
Short circuit :
Signal (Static)
• Remote control
prohibiting
operation is prohibited.
remote control
Open circuit :
• Remote control
operation is permitted.
Input 1:
Open circuit
Start/stop signal
→ Short circuit (300 ms or
(Pulse)
more) → With Open,
the start/stop status is
reversed.
(Start
Stop)
Input 2:
Short circuit :
Signal (Static)
• Remote control opera
prohibiting
tion is prohibited.
remote control
Open circuit :
• Remote control
operation is permitted.
Switch No.
1 2 3 4 5 6
1 2 3 4 5 6
33
49
34
50
35
51
36
52
37
53
38
54
39
55
40
56
41
57
42
58
43
59
44
60
45
61
46
62
47
63
48
64
Status
SW5 SW6
ON
OFF
ON
ON
Switch No.
Address setting
switch (SW001)
Switch No.
Function setting
switch (SW002)
*:Factory setting
Contact input
External equipment
details
operation details
Input 1:
Short circuit :
Card key/Coin
• Remote control operation is
timer signal
permitted.
Open circuit :
• Room air conditioner stops.
• Remote control operation is
prohibited.
• All operation using the
central control device is
permitted.
Input 2 : Not in use
Input 1:
Short circuit :
Emergency
• Room air conditioner stops.
stop signal
• Remote control operation is
prohibited.
• Operation using the
central control device is
prohibited.(Start / stop
and changing the remote
control prohibition setting
are prohibited.)
Open circuit :
• Remote control operation is
permitted.
Input 2 : Not in use
OFF ON
−
−