4. Installing the product
DANGER
Death or serious personal injury
‐
Before installation, make sure that the
power supply is switched off and it can-
not be switched on unintentionally.
WARNING
Death or serious personal injury
‐
Installation must be carried out by
qualified staff.
WARNING
Death or serious personal injury
‐
Use appropriate tools and safety
equipment when handling the product.
CAUTION
Minor or moderate personal injury
‐
Use a proper lifting method when nec-
essary.
Electro-magnetic compatibility (EMC)
The drive must comply with the standard IEC
61000-3-12. The short-circuit power SSC must be a
minimum of 120 RSCE at the interface point between
your and the public mains. Make sure to connect the
drive and the motor to the mains with a short-circuit
power SSC that is a minimum of 120 RSCE. If
necessary, contact your mains operator.
Using an RCD or an RCM device
The drive can cause a current in the protective
grounding conductor. Use a residual current-operated
protective (RCD) device, or a residual current-
operated monitoring (RCM) device to give protection
against a direct or an indirect contact. Use a type B
RCD or RCM device on the mains side of the drive.
Adjust the minimum frequency to a value
that ensures water is discharged from the
outlet of the pump.
To adjust the minimum frequency, click the
Home button on the control panel and se-
lect minimum frequency.
To ensure a proper convective cooling ef-
fect, install the RSI according to fig. Instal-
lation example showing the required clear-
ance when mounting the product.
Do not install the equipment in direct sun-
light.
CAUTION
Minor or moderate personal injury
‐
Ensure that the mounting wall can sup-
port the weight of the inverter. See the
weight in
3.2 Technical
Related information
3.2 Technical data
4.1 Installation example
data.
17