Zero-Point Adjustment; Ordering Codes - Johnson Controls DP2500-R8 Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 14
English
Wiring
WARNING: Risk of Electric Shock and Property Damage.
Disconnect each of multiple power supplies before making electrical connections. More than one
disconnect may be required to completely de-energize equipment. Contact with components
carrying hazardous voltage can cause electric shock and may result in severe personal injury or
death.
WARNING: Use this sensor only as an operating control.
Where failure or malfunction could lead to personal injury or damage to the controlled equipment
or other property, additional precautions must be designed into the control system. Incorporate
and maintain other devices such as supervisory or alarm systems or safety or limit controls that
are intended to warn of, or protect against, failure or malfunction of the sensor.

Zero-point adjustment

IMPORTANT: Supply voltage must be connected one hour before the 0-point adjustment
is carried out.
1) Loose both tubes from the pressure inlets + and -
2) Push zero button > 4 seconds until the red led turns ON.
3) Wait until LED turns off and then install tubes again to the pressure inlets.
It is recommended to adjust the zero point every 12 months during normal operation.
* If the transmitter is equipped with automatic zero element the manual push button adjustment is not
required.
Optional auto zero element
Optional auto zero element makes the DP transmitter maintenance free for periodical push button
zeroing. Element automatically adjusts the transmitters zero point from time to time, this eliminates the
zero point long term drift of the piezoresistive sensing element.
Zero point adjustment is carried out every 10 minutes. During zero point adjustment the output and display
values will freeze to the latest measured value. The automatic zero point adjustment takes 4 seconds.

Ordering Codes

Item Codes
DP2500-R8
DP2500-R8-AZ
DP2500-R8-D
DP2500-R8-AZ-D
Description
Differential Pressure Sensor,
with 8 Ranges
Differential Pressure Sensor,
with 8 Ranges
and Auto Zero feature
Differential Pressure Sensor,
with 8 Ranges and Display
Differential Pressure Sensor,
with 8 Ranges
and Auto Zero feature and Display
--
--
--
X
--
--
X
--
--
X
X
--
This document is subject to change without notice
IS_DP2500-R8 Rev. A_11 2009
Selectable Range in Pa
X X X X X X X X
X X X X X X X X
X X X X X X X X
X X X X X X X X
2

Publicidad

Tabla de contenido
loading

Tabla de contenido