Technical Specifications

Response Time
Accuracy
Bursting pressure
Suitable media
Measuring element
Electrical interface (3-wire)
- Supply voltage 24 VAC or VDC
- Max. tolerance ±10%
- Power consumption <1.0 W (<1.5W with Iout 20 mA)
- Output signal 0...10 VDC, Load R minimum 1kΩ or
Materials
- Pressure connections ABS
- Duct connectors ABS
Connections
- Electrical connections 4 screw terminals, max 1.5 mm
- Pressure connections Male ∅ 5,0 mm and 6,3 mm
Weight
Dimensions
General ambient condition
Temperature range
- Ambient humidity 0 to 95% RH
Safety
- Protection standard IP54
- Conformance Meets the requirements for CE marking:
0.8 / 4 s selectable push button
±1,5% or (±6 Pa < 250 Pa) of selected pressure range
30 kPa
Air and non-aggressive gases
Piezoresistive
4...20 mA, maximum load 500Ω
- Housing ABS
- Cover PC
- Tubing PVC, soft
- Cable entry M16
150 grams, with accessories 290 grams
90,0 x 71,5 x 36,0 mm
- Operation -10...+50 °C (-5...+50 °C for -AZ model)
- Storage -20...+70 °C
EMC directive 2004/108/EC
Rohs Directive 2002/95/EY