Technical Data; Description; Initial Operation; Maintenance - oventrop OV-DMPC Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 11
3.2 Storage
The measuring system must only be stored under the
following conditions:
– Do not store in open air, keep dry and free from dust.
– Do not expose to aggressive fluids or heat sources.
– Protect from direct sunlight and mechanical agitation.
– Storage temperature:
relative humidity of air:
ATTENTION
No water may remain in the measuring transmitter
where there is a risk of frost
In this case, the "DMPC-sensor" and measuring
hoses must be drained completely.

4 Technical data

4.1 Performance data
Max. operating temperature: 120 °C
Min. operating temperature: - 20 °C
Max. operating pressure:
Max. differential pressure:
Fluid: Water and suitable water and glycol mixtures
according to VDI 2035. Not suitable for steam, oily and
aggressive fluids.
DANGER
Suitable measures (e.g. safety valves) have to be
taken to ensure that the maximum operating pres-
sures and maximum and minimum operating tem-
peratures are not exceeded or undercut.
4.2 Materials
Body and cover made of aluminium. Measuring hoses
made of plastic, connection couplings and measuring
adapter made of brass.
4.3 Dimensions / Weights
Measuring case with
accessories:
310 x 310 x 90 mm / 2500 g
"DMPC-sensor": 130 x 55 x 60 mm / 1000 g

5 Description

5.1 Application
The measuring system serves to measure differential
pressures/flow rates and temperatures in central heating
and cooling systems with closed water circuits as well
as the hydronic balance.
5.2 Markings
Information on the "DMPC-sensor":
OV
Oventrop
123456 Serial number
DMPC Marking
0600
4
–20°C up to + 60°C,
max. 95 %
16 bar (1600 kPa)
see adhesive label on
the unit
(e.g. 0600=600 mbar)
Differential pressure range

6 Initial operation

The national and local guidelines as well as the approved
rules of technology must be observed during initial ope-
ration.
6.1 Minimum system requirements - computer:
Processor 1.5 Ghz
Hard-disk storage capacity 40 MB
Main memory RAM for Windows XP 256MB
Main memory RAM for Windows Vista 512MB
Main memory RAM for Windows 7 1024MB
Screen resolution 1024 x 600 pixel
1x USB slot 2.0
6.2 Software installation
Install "OV-DMPC" software stored on the enclosed USB
stick.
If the "OVplan" and/or "OVselect" link shall be used,
the required software which is also stored on the USB
stick, has to be installed, too.
Updates are available at www.oventrop.com.
6.3 Operating instructions "OV-DMPC"
The operating instructions can be selected from any
page of the "OV-DMPC" measuring programme via the
?
help symbol ? .
ATTENTION
Read the operating instructions in their entirety be-
fore connecting the "DMPC - sensor".
6.4 Connection of the "DMPC-sensor"
The "DMPC-sensor" is connected to the USB slot (2.0)
of the computer via the enclosed USB cable. Further
advice regarding the operation of the "DMPC-sensor"
is detailed in the operating instructions. It can be se-
lected from any page of the "OV-DMPC" measuring sys-
tem via the help symbol ? .
The following advice must be observed when connecting
the "OV-DMPC" to central heating or cooling systems.
NOTE
Provide free water flow through measuring
hoses. Should the strainers of the "DMPC-sensor"
be heavily polluted, they have to be cleaned or re-
placed.
After installation, check all installation points for leaks.

7 Maintenance

Correct use is paramount for a trouble-free operation of
the measuring system.
The measuring system has to be calibrated once a year.
For this purpose please return the measuring system to
the following address:

8 Warranty

Oventrops warranty conditions valid at the time of supply
are applicable.
?
Oventrop
Industriegebiet Nord
Hinterm Gallberg 5
D-59929 Brilon

Publicidad

Tabla de contenido
loading

Tabla de contenido