Level Switch - Elko EP HRH-1 Manual De Instrucciones

Ocultar thumbs Ver también para HRH-1:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 25
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
www.elkoep.com
Made in Czech Republic
02-17/2017 Rev.: 0
Characteristics
• used to control the level in wells, reservoirs, tanks, pools, tankers, containers, etc.
• within the framework of a single device, the following confi gurations can be selected
(see functions graph):
- two separate level switches
- two probes in one tank
- fi lling tank from well
• single-state monitors one level (full or empty tank), double-state monitors two levels
(switches on upon one level and switches off upon the second)
• DIP switch on front panel is used to choose function (see functions graph):
- pumping in
- pumping out
- over-pumping
• option of setting time delay for reacting to the output upon a change in level, any type
of delay by DIP switch
• sensitivity adjustable by potentiometer (probe resistance based on fl uid)
• the measuring frequency 500 Hz prevents fl uid polarization and oxidation increase of
measured probes
• galvanically separated supply AC 110 V, AC 230 V or AC/DC 24 V
• output contact 2x switches 16 A / 250 V AC1
• 3-MODULE design, mounting onto DIN rail
Description
1
2
3
4
5
6
cos φ ≥ 0.95
Type of load
AC1
Mat. contacts AgNi,
contact 16A
250V / 16A
Type of load
AC13
Mat. contacts AgNi,
contact 16A
250V / 6A
1. Terminal for connection of conductor
7
common for both probes
8
2. Supply voltage terminals
3. Supply voltage indication
9
4. H relay indication (OUT2)
10
11
5. D relay indication (OUT1)
12
6. Output contact of D relay - OUT1
13
7. Terminals for connecting probe
8. Terminals for connecting shield
14
9. Single / double relay function
15
10. Relay D function inversion
11. Relay D delay type selection
12. Relay H delay type selection
13. Delay setting relay H
14. Delay setting relay D
16
15. Sensitivity setting of probe according to
resistance of measured fl uid
16. Output contact of H relay - OUT2
M
M
AC2
AC3
250V / 5A
250V / 3A
K
AC14
AC15
250V / 6A
250V / 6A
HRH-1

Level switch

Symbol
Connection
AC5a
AC5a
uncompensated
compensated
x
230V / 3A (690VA)
M
DC1
DC3
24V / 16A
24V / 6A
1 / 3
A1
16
18
28 26
C
D
H
S
A2
15
Un
A1 A2 C D H
S
16 15 18 28 25 26
HAL.230V
AC5b
AC6a
800W
x
250V / 3A
M
DC5
DC12
24V / 4A
24V / 16A
EN
25
AC7b
AC12
250V / 10A
DC13
DC14
24V / 2A
24V / 2A

Publicidad

Tabla de contenido
loading

Tabla de contenido