Technical specifications |
Type
Output
steps
[kW]
0/4.5/9
AR310E09
0/7/13.5
AR315E14
0/9/18
AR320E18
Technical specifications |
Type
Output*3
[kW]
16
AR310W
23
AR315W
33
AR320W
Protection class AR 300 E/W above false ceiling: IP44, below false ceiling: IP20
GB
*1) ∆t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*2) Conditions: Distance to the unit: 5 metres. Directional factor: 2. Equivalent absorption area: 200 m
*3) Applicable at water temperature 80/60 °C, air temperature, in +15 °C.
10
Thermozone AR 300 E with electrical heat
∆t*¹
Airflow
[m³/h]
[°C]
1000/2000
27/14
1400/2800
29/15
2000/4000
27/14
Thermozone AR 300 W with water heat
∆t*¹,*³
Airflow
[m³/h]
[°C]
1000/2000
30/23
1400/2800
31/24
2000/4000
31/25
AR 300 E/W
3
Sound
Voltage
level*²
Amperage
[dB(A)]
(control)
43/59
230V~ / 2,1A
43/60
230V~ / 2,9A
46/63
230V~ / 4,2A
2
Sound
Voltage
level*²
[dB(A)]
[V]
43/58
230V~
43/59
230V~
46/62
230V~
Voltage
Weight
Amperage
(heat)
[kg]
400 V3~ / 13 A
42
400 V3~ / 19,5 A
58
400 V3~ / 26 A
78
Amperage
Weight
[A]
[kg]
2,1 A
42
2,9 A
58
4,2 A
78
.
2