5.4

Mounting the siren to the wall

1.
Hold the mounting template in position and mark the positions of
the mounting holes. If necessary, use a spirit level.
2.
Drill mounting holes (6 mm) into the wall according to the marked
positions.
3.
Insert a supplied wall plug into each mounting hole.
4.
Install the screws (30 mm) into the top mounting holes, leaving
approximately 9 mm of the screw protruding.
5.
Install the mounting plate. Make sure that the holes in the
mounting plate align with the bottom mounting holes.
6.
Install the screws (25 mm).
7.
Mount the siren to the wall.
CAUTION:
Make sure that the tamper switch is closed when you mount the siren
to the wall. If the tamper switch does not close, the siren will not
operate correctly. If necessary, remove the siren again and insert a
spacer between the tamper switch plunger and the wall to make sure
that the switch closes when you mount the siren to the wall.
CAUTION:
Before testing or operating the siren, leave it in position for at least
24 hours in order to fully charge the battery.