Ocultar thumbs Ver también para CFW-11:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6. OTHERS

ATTENTION!
The parameter P0352 (Fan Configuration) must be set at 1 or 4 for the CFW11 XXXX X X
O 54 ... inverters.
NOTES!
- The CFW11 XXXX X X O 54 ... models are supplied with the parameter P0352 adjusted in
4, i.e., the heatsink fan is controlled based in the IGBT/rectifier temperature and the internal
fan is always activated.
- If the factory settings are loaded (via P0204) and the inverter software version is equal
or prior to V1.6x, the parameter P0352 is adjusted automatically in 2. In this case, for the
CFW11 XXXX X X O 54 ... inverters, adjust this parameter again in 1 or 4.
ATTENTION!
The following items from the user's guide do not apply to the CFW11 XXXX X X O 54 ...
inverters:
- Flange mounting described in the section 3.1.3;
- Figure 3.5 (section 3.1.4) of the CFW-11 inverters frame sizes A...D user's guide;
- Sections 3.1.4 to 3.1.7 of the CFW-11 inverters frame size E user's guide;
- Frame sizes 1 and 2 inverters: values for surrounding air temperature = 50 °C (122 °F)
of the table 8.2;
- Frame size 3 inverters: values presented in the tables 8.2 and 8.4;
- Protection degree specification of the section 8.2.
NOTE!
The CFW11 XXXX X X O 54 ... models are not UL listed.
15

Publicidad

Tabla de contenido
loading

Tabla de contenido