Dependencies F-DI 8x24VDC HF (6ES7136-6BA00-0CA0)
General dependencies
The following applies to the "Input delay" parameter, depending on the sensor supply and activation of the short-circuit test:
"Input delay" < MIN ("Startup time of the sensor after a short-circuit test", "Time for the short-circuit test").
The "Startup time of the sensor after a short circuit test" must be configured to be at least 1% of the "Time for the short circuit
test".
If a sensor supply is selected for a channel, this sensor supply must also be activated. You also need to disable unused
encoder supplies.
Reintegration after a channel fault depends on the F-host used. You can find information on this in the documentation of the
F-host. The F module supports configuration per GSD file PROFIsafe V2.4.
When configuring with GSD file, only module-wide passivation is possible.
Dependencies for 1oo2 evaluation
Both channels must be activated.
The "Input delay" parameter must be identical for each pair. The "Input delay" parameter for the channel pair is determined as
follows:
"Input delay" < MIN("Input delay" for channel n, "Input delay" for channel n+4).
The configured discrepancy time must be greater than the configured input delay.
Disable chatter monitoring for both channels.
Dependencies F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
The same dependencies apply to this F-module as for F-DI 8x24VDC HF (6ES7136-6BA00-0CA0).
In addition, channel-by-channel passivation is also possible due to the support of PROFIsafe V2.6.1.
Dependencies F-PM-E 24VDC/8A PPM ST (6ES7136-6PA00-0BC0) as
of firmware version V2.0.0
The same dependencies apply to this F-module as for the two F-modules with article numbers 6ES7136-6DB00-0CA0 and
6ES7136-6BA00-0CA0 described above.
In TIA Portal, the "IO Tags" tab displays more tags than supported by the F module.
Dependencies F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)
If you have enabled "Disable dark test for 48 hours", you must configure the "Max. readback time light test / dark test"
parameter the same for all channels.
Reintegration after a channel fault depends on the F-host used. You can find information on this in the documentation of the
F-host. The F module supports configuration per GSD file PROFIsafe V2.4.
When configuring with GSD file, only module-wide passivation is possible.
Dependencies F-RQ 1x24VDC/24..230VAC/5A
(6ES7136-6RA00-0BF0)
The F module has no F_iPar_CRC and no PROFIsafe address. You do not need to assign a PROFIsafe address to the F module.
If you nevertheless assign a PROFIsafe address to the F module with S7-FCT, an error message is displayed.
Dependencies during configuration with GSD files for ET 200SP fail-safe modules
8