The code word 0000 causes the AS-i safety monitor to switch the
installation into the safe state.
In the configuration software for the safety monitor the module must
be used for the evaluation unit as double-channel forced module. For
further details please see the configuration software manual (see
chapter "Monitoring devices").
Addressing
The evaluation unit can be addressed via the AC1154 addressing unit.
Assign a free address between 1 and 31. At the factory the address is
set to 0.
If it is used with the FC lower part, e.g. AC5000 (without addressing
socket) the module must first be addressed via the AC1154 addressing
unit and then mounted onto the lower part.
Infrared addressing
The evaluation unit also offers the option of infrared addressing with
the AC1154 addressing unit.
The AS-i communication (yellow cable) must be switched off
during the infrared addressing. To do so, disconnect the master.
Supply the slaves with voltage via the AS-i power supply. Addressing is
carried out via the IR addressing cable E70211.
When the ifm AS-i power supplies type SL are used, the
communication can be deactivated via a jumper on the power supply.