The compressor doesn't
start
The compressor runs but
makes no ice
Water line
Water inlet
Water pump
Drainage tray on top of
the compressor
Wiring connects
The start relay/thermal
protect
The startup coil / running
coil
Condenser
Fan
The Electronic controller
Refrigerant
Troubleshooting
The water line leaks.
The water line is blocked. Clean it, see user manual
Water supply pressure is
low.
The water inlet is blocked. Check and clear it
Water pump damaged.
The room temperature is
out of the stated range,
the water pump stops
automatically.
The lines of the water
pump are loose.
The housing of water
pump leaks.
Drainage tray on top of
the compressor is full.
It's loose.
It's damaged.
It's turned off.
The motor of the
compressor has short
circuited.
The condenser may be
dirty.
The fan may be dirty or
damaged
The controller is damaged Replace the Electronic
Refrigerant leaks
completely.
15
Plug in again.
"ice making system
cleaning"
Adjust the water supply
pressure within the stated
range.
Replace water pump.
Make the temperature
return within the stated
range.
Plug in again.
Replace water pump.
Drain off water by
unscrewing lower
drainage nut.
Plug tightly, or replace.
Replace the start relay/
thermal protect of the
compressor.
Replace the compressor.
Replace the compressor.
Clean the condenser.
Clean or Replace the fan.
controller.
Add low side access
valve, locate leak, recover
refrigerant, replace drier,
evacuate and weigh in
the data plate charge.