• Single-phase equipment (230V) connected to the generator does not work:
Is the "OVERLOAD" pilot
activated?
YES
Using a voltmeter, is the 230V socket showing voltage?
Disconnect all equipment from the generator. Stop the generator and
start it again.
If the engine continues without generating electricity, contact our
Technical Assistance Service: spv@sg-group.es
Check if the equipment
connected to the generator
has any failure.
YES
NO
NO
49
Press the "RESET" button to
reset the 230V output.