Lutron GRAFIK Eye GRX-IO Instrucciones De Instalación página 3

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 9
Low-Voltage PELV (Class 2: USA) Wiring
Important Notes
Install in accordance with all applicable regulations.
CAUTION: Do not connect line voltage/mains power to
device. Improper wiring can result in personal injury or
damage to the device or to other equipment.
This control can use PELV (Class 2: USA) wiring
methods. Check with your local electrical inspector for
compliance with national and local codes and wiring
practices.
GRX-IO Control Interface Wiring:
GRX-3000 or GXI-3000 Control Unit
Rear View of GRAFIK Eye Control Unit
(GRX-3106 shown)
ZONE 2
ZONE 4
CU WIRE ONLY
ZONE 6
CLASS 2
USA
Class 2
1 2 3 4
HOT/LIVE
IEC
PELV
SSA
Use Lutron Cable
GRX-CBL-346S
or equivalent
OMX-IO Control Interface Wiring: Control Station Device Link
or
GRX-IO Control Interface Wiring: GRX-4000 Control Unit
Data Link: (1) shielded, twisted
pair #18 AWG (1.0 mm
4: MUX
3: MUX
Use Lutron Cable
GRX-CBL-46L
PELV (Class 2: USA)
Power wiring:
1: Common
2: 24 V
Power
2
(2) #18 AWG (1.0 mm
) pigtails,
6 in. (152 mm) maximum length
R
Data Link:
ZONE 1
4: MUX
ZONE 3
3: MUX
ZONE 5
One shielded, twisted
pair #18 AWG
(1.0 mm
NEUTRAL
for data link
(terminals 3 and 4)
PELV (Class 2: USA) Power wiring:
2: Power
1: Common
Two #18 AWG (1.0 mm
for Common (terminal 1) and
12 V
(terminal 2)
2
)
D: Drain/Shield
(2) #12 AWG
2
(2.5 mm
)
(2) #12 AWG
2
(2.5 mm
)
• Make daisy-chain connections to the low-voltage PELV
(Class 2: USA) Data Link terminals on the end of the
Control Interface.
• Do not use T-taps. Run all wires in and out of the terminal
block, or use a short pigtail, as shown below.
• Each terminal accepts up to two #18 AWG (1.0 mm
wires.
Data
Link
2
)
To additional Wallstations/Control Interfaces
(16 maximum; 3 powered from one GRAFIK Eye
Control Unit without external 12 V
supply)
2
) conductors
GRX-IO counts as two devices toward the
maximum of three connected to one GRAFIK Eye
3000 control unit
(Data Link connection shown)
Note: Do not connect Drain/Shield to Earth/Ground
or Wallstation/Control Interfaces. Connect the bare
drain wires and cut off the outside shield.
Note: #12 AWG (2.5 mm
Common (terminal 1) and 24 V
(terminal 2) will not fit in terminals; use #18 AWG
2
(1.0 mm
) pigtails (< 6 in./152 mm).
GRAFIK Eye
and GRAFIK Systems Installation Instructions
®
power
2
) conductors for
Power
2
)
3

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Grafik eye omx-ioGrafik eey grx-ioGrafik eey omx-io

Tabla de contenido