Low-Voltage PELV (Class 2: USA) Wiring
Data Link (to control units,
processors, and wallstations)
4: MUX
3: MUX
2: 12 - 24 V
1: Common
Contact Closure Ratings
Five Input Terminals
•
Accept maintained inputs and momentary inputs with 40 msec minimum pulse times.
•
Off-state leakage current must be less than 100 uA.
•
Open circuit voltage: 24 V
•
Inputs must be dry contact closure, solid state, open collector, or active-low
(NPN)/active high (PNP) output.
- Open collector NPN or active-low on-state voltage must be less than 2 V
3.0 mA.
- Open collector PNP or active-high on-state voltage must be greater than 12 V
source 3.0 mA.
Five Output Terminals
•
Provide maintained or momentary (1-second) outputs.
•
The GRX-IO and OMX-IO are not rated to control unclamped, inductive loads.
Inductive loads include, but are not limited to, relays, solenoids, and motors. To control
these types of equipment, a flyback diode must be used (DC voltages only). See
diagram.
4
GRAFIK Eye
and GRAFIK Systems Installation Instructions
®
1 2 3 4 5 6 7
LED 1: CCO 1
LED 2: CCO 2
LED 3: CCO 3
LED 4: CCO 4
LED 5: CCO 5
LED 6: Unused
LED 7: Link status
maximum.
Program button
(not used on OMX-IO)
DIP
switches
Note: LED is ON when CCO NO
(normally open contact) is closed.
and sink
and
GRX-IO
or
OMX-IO
CCO and CCI connectors hold one #28 -
16 AWG (0.08 - 1.5 mm
) wire
2
Output Ratings
Supply
Voltage
0 - 24 V
0 - 24 V
Flyback
Diode
OMX-IO
Output
Resistive
R
Load
1.0 A
0.5 A
Inductive
Load
+
DC
-
R