3.4 Troubleshooting

Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the display will flash together
with the fault symbol (detail 20 - fig. 1) indicating the fault code.
There are faults that cause permanent shutdowns (marked with the letter "A"): to restore operation press the RESET
button (detail 8 - fig. 1) for 1 second or use the RESET on the optional remote timer control if installed; if the boiler fails
to start, it is necessary to first eliminate the fault.
Other faults (marked with the letter "F") cause temporary shutdowns that are automatically reset as soon as the value
returns within the boiler's normal working range.
Table. 5 - Fault list
Fault
Fault
code
A01
The burner fails to light
Flame present signal with
A02
burner off
Overtemperature protection
A03
activation
Fume extraction duct safety
A04
device activation
A05
Fan protection activated
No flame after ignition
A06
stage (6 times in 4 minutes)
F07
High fume temperature
F10
Delivery sensor 1 fault
F11
Return sensor fault
F13
Fume sensor fault
24
All manuals and user guides at all-guides.com
Possible cause
No gas
Ignition/detection electrode fault
Faulty gas valve
Insufficient gas supply pressure
Trap clogged
Electrode fault
Card trouble
Heating sensor damaged
No water circulation in system
Air in the system
Fault F07 generated 3 times in
the last 24 hours
Fault F15 generated for 1 hour
(consecutive)
Ionisation electrode fault
Flame unstable
Gas valve Offset fault
air/fume ducts obstructed
Trap clogged
Flue partially obstructed or insuf-
ficient
Fume sensor position
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
cod. 3540M640 - 07/2008 (Rev. 00)
ENERGY TOP W 70
Cure
Check the regular gas flow to the boiler and that the air
has been eliminated from the pipes
Check the wiring of the electrode and that it is correctly
positioned and free of any deposits
Check and replace the gas valve
Check the gas supply pressure
Check the trap and clean it if necessary
Check the ionisation electrode wiring
Check the card
Check the correct positioning and operation of the
heating sensor
Check the circulating pump
Vent the system
See fault F07
See fault F15
Check the position of the ionisation electrode and
replace it if necessary
Check the burner
Check the Offset adjustment at minimum power
Remove the obstruction from the flue, fume extraction
ducts and air inlet and terminals
Check the trap and clean it if necessary
Check the efficiency of the flue, fume extraction ducts
and outlet terminal
Check the correct positioning and operation of the
fume sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor