To change the heating and/or cooling curve:
1. Press and hold the OK button on the controller for
about 10 seconds to enter the system parameters
menu.
2. The settings icon is displayed in the top left hand
corner of the display, and the text Hot type, Cld
type, or rEv type (depending of current operating
mode) is displayed.
3. Use buttons < or > to locate parameter 1 (Cur)
– Heating curve, or 1 (Cur) – Cooling curve. They
are identifi ed using the heating or cooling symbol.
Heating curve:
Default: 0.7
Setting range: 0.1 – 5, 0.1 increments
Cooling curve:
Default: 0.4
Setting range: 0.1 – 5, 0.1 increments
4. Use buttons - or + to change parameter setting.
5. Press the OK button on the controller to confi rm
the change and return to the system parameter
settings.
6. Repeat steps 3 through 5 to change the other curve
settings, if needed.
Factory reset
To perform a factory reset, go to system parameter 23
(ALL) – Factory reset, in the controller.
Press and hold the OK button for about 5 seconds until
the controller restarts.
See section Setup the system for more information.
U P O N O R S M AT R I X M O V E P L U S · Q U I C K G U I D E
All manuals and user guides at all-guides.com
Q U I C K G U I D E
System integration with other systems
(Move PLUS only)
The Uponor Smatrix Move PLUS controller can be
integrated with another Uponor Smatrix Wave/Wave
PLUS/Space/Space PLUS system to enhance the
capabilities of the full climate system. At the same
time, the integration removes the need of a separate
thermostat, and outdoor sensor, for the Move PLUS
system.
Shared information
Information regarding system state and reference room
temperature is forwarded to the Move PLUS controller,
which adjusts the supply temperature accordingly.
Different system states and temperatures which can be
forwarded are:
•
Comfort/ECO mode*
•
Heating/cooling mode
•
Holiday mode*
•
Reference room temperature and setpoint
•
Outdoor temperature (if installed in the thermostat)
•
Remote sensor (if installed in the thermostat)
•
Indication if the relative humidity exceeds set limits
(requires the digital thermostat T-167 or T-168)
*)
Through change of setpoint, using the ECO setback value from the
integrated system. No indication or change of mode is shown in the
Move PLUS controller.
The integration is activated when the thermostat is
registered to both controllers (Move PLUS and Wave,
Wave PLUS, Space, or Space PLUS).
See the Uponor Smatrix Wave/Wave PLUS
documentation on how to register the thermostat to a
Wave/Wave PLUS system.