MEMORIZATION PROCEDURE
WARNING: After powering the control panel, wait 2 seconds before you start perform-
ing the adjustment operations.
The gate must be equipped with the opening and closing safety stops.
When you have completed the installation procedures :
1_ bring the gate to approx. 1 m from the closing travel limit;
2_ set dip-switch no. 10 to ON;
3_ operate the automation using one of the following inputs: A/C, radio control or card button (PROG);
4_ the gate must start to close.
If it opens, stop the programming procedure by resetting the electric panel (disconnect
the power supply to the panel for at least 5 sec. and set dip-switch no. 10 to OFF); with
the control panel disconnected, exchange the motor supply wires. Restart the proce-
dure from point 1.
5_ when the gate has closed, after approximately 2 seconds a complete opening manoeuvre is ex-
ecuted automatically;
6_ when the gate has opened, wait for the DL3 led to be fixedly on, then set dip-switch no.10 to OFF;
7_ the automation is now ready for operation.
Make the logic adjustments.
When any adjusting devices (trimmers or dip-switches) on the control panel are oper-
ated, a complete manoeuvre must be carried out in order for the new settings to take
effect.
LOGIC ADJUSTMENTS
TRIMMER
RALL.
Deceleration adjustment: from 50 to 120 cm before the limit switch;
Note: the automation must perform a complete opening and closing manoeuvre
before setting the deceleration.
FR.
Obstacle detection sensitivity adjustment. The trimmer is set to provide sufficient thrust to
work the gate without exceeding the limits established by current standards (EN 12453).
Turning the trimmer clockwise (+) increases the motor torque, turning it anticlock-
wise (-) reduces it.
T.C.A.
Automatic Closing time adjustment: from about 3 to 255 seconds (see dip-switch no. 1);
Dip switch
AUTOMATIC
1
CLOSING
2
2 / 4 STROKE
OPENING
3
PHOTOCELLS
OPERATION
4
NO REVERSE
PRE-
5
FLASHING
PHOTOCELL
6
TEST
after opening, the gate automatically closes when the delay set on the
On
T.C.A. trimmer expires.
Off
automatic closing disabled.
with automatic closing enabled, a sequence of open/close commands
On
causes the gate to OPEN-CLOSE-OPEN-CLOSE etc (see also dip
switch 4).
in the same conditions, the same command sequence causes the
Off
gate to OPEN-STOP-CLOSE-STOP-OPEN-STOP (step-by-step).
during opening, the photocell cuts in to stop the gate until the obstacle
On
is removed. When the obstacle is removed the gate resumes opening;
Off
during opening, the photocell does not cut in.
the open-close pushbutton reverses the direction of movement of the
On
gate even while it is opening.
NO-REVERSE function activated; the gate ignores the closure com-
Off
mands during opening and reversal of movement occurs only during
closure;
On
the pre-flashing function enabled.
Off
the pre-flashing function disabled.
On
the "photocell test" function is enabled;
the "photocell test" function is disabled.
Off
Note: to be used when the photocells are not used.
K125M
17