FireClass FC410MIO Manual De Instrucciones página 2

Ocultar thumbs Ver también para FC410MIO:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

FC410MIO
Tyco Fire & Security GmbH,
Victor von Bruns-Strasse 21,
8212 Neuhausen am Rheinfall,
Switzerland
DoP-2015-4017
EN54-18
Input/output device for fire detection and fire
alarm systems for buildings
FC410MIO
Essential Characteristics
Performance under fire condition: Passed
Operational reliability: Passed
Durability of operational reliability; temperature
resistance: Passed
Durability of operational reliability; humidity
resistance: Passed
Durability of operational reliability; corrosion
resistance: Passed
Durability of operational reliability; shock and
vibration resistance: Passed
Durability of operational reliability; electrical
stability: Passed
Durability of operational reliability; resistance to
ingress: Passed
2/16
0832
09
Verdrahtung
1 Es müssen keine DIP-Schalter oder Steck-
brücken-Einstellungen vorgenommen wer-
den.
2 Alle Leitungen müssen erdfrei sein.
3 Stellen Sie die korrekte Polung der Verka-
belung sicher, bevor Sie das FC490ST an die
Ringleitungsspannung anschließen.
4 Die Abb. 3 und Abb. 4 zeigen typische Verdra-
htungsbeispiele für das FC410MIO.
PORTA DI PROGRAMMAZIONE
PROGRAMMING PORT
ANSCHLUSSBUCHSEN FÜR
FC410MIO
HANDPROGRAMMIERGERÄT FC490ST
HVR800-Treiber
HVR800-Drivers
Abb. 1: Multi-Ein-/Ausgangsmodul FC410MIO
Typische verdrahtungsbeispiele für
das FC410MIO
Siehe hierzu Abb. 3 und Abb. 4.
Hinweise zu Abb. 3:
1 Alle Eingänge der Stichleitung müssen mit
einem 330-?
-EOLWiderstand abgeschlossen werden.
2 Betriebsart (mit FireClass Console einstell-
bar):
Störung bei Kurzschluss (Schließer)
3 Ein Kontakt für jede Stichleitung.
Montagehinweis
Fixing Instructions Doc. version 6.0
FireClass
INGRESSI SPUR
SPUR INPUTS
Dok.-Version 6.0

Publicidad

Tabla de contenido
loading

Tabla de contenido