DIAGNOSTIC INDICATION
Phase indicator LEDs (Green)
Each phase is equipped with a green LED. Should
complete loss of surge protection occur on each
phase, the green LED will extinguish and the red
service LED will flash. Every suppression element
is monitored. Note that the green LED indicators
will drop out due to loss of power or severe under
voltage.
Service LED (Red)
Flashes in the event of a problem. The red service
LED is slaved to the green LEDs via logic and will
illuminate when any green LED extinguishes.
Audible Alarm Option
If equipped with optional Dry Contact and Audible
Alarm, these options are slaved via logic to the
green LEDs. In the event of a problem, the Dry
Contacts will change state and the Audible Alarm
will sound. The Audible Alarm may be silenced by
deenergizing the SPD.
Optional Remote Display Models
Overview: All Remote Display models include Per
Phase green LEDs, red service LED, Push to Test
function, Audible Alarm, Silence Switch with LED
indicator, and one set of Form C Dry Contacts.
Remote Display XDSs include unique internal
connections specific for the Remote Display.
Remote Displays are not retrofitable in the field to
non-Remote Display XDS models.
Figure 7
OPTIONAL REMOTE DISPLAY DIMENSIONS
3.690
3.437
0.000
0.250
8
Advanced Protection Technologies
Phase A
Phase B
Phase C
Service
Test
The Remote Display is rated NEMA 4 and
includes a sealing gasket. It is connected via a 4'
multi-pin ribbon cable. The Remote Display
requires a cutout through non-combustible
material such as metallic plate.
R: Standard Remote Display
S: Remote Display with Surge Counter and
Counter Reset function and Eprom memory
T: Remote Display with separate N-G LED
(N-G is otherwise monitored with Phase A)
U: Remote Display with separate N-G LED and
Surge Counter
Mounting Diagnostic Display
Mount the Display in a user-friendly location,
with consideration to weather and vandalism.
Dimensions are in Figure 7. A 4' connector
cable is typically included. Longer lengths are
available. The Display features a UL94-5VA and
UL 746C(f1) polymeric label. A gasket is included.
Diagnostic Display Operation
All indicators and controls are located on the
Diagnostic Display. Each phase features a green
LED indicator. Green LEDs indicate correct
operation. If an inoperative condition were to
occur, the built-in Audible Alarm will sound and
the red service LED will illuminate. This indicates
that the unit needs evaluation by a qualified
electrician or technician. Until a qualified person
evaluates the unit, press Silence to silence the
alarm. (The LED above Alarm Silence illuminates
when the alarm is deactivated. Normal operation
occurs with the Alarm Silence LED extinguished.)
Silence
8159B
.180 THRU 4 PL.
RC .375 4 PL.