Descargar Imprimir esta página

Loading The Programme Into The Control Panel - De Dietrich AD264 Manual Del Usuario

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 102

4.3 Loading the programme into the control panel

Power up the control panel.
Press the
key until LoAd is displayed.
Press the OK key.
Wait a few seconds.
The progress bar will show you the progress of programming.
If a problem occurs during the update, the error message
LoAd : Er x is displayed.
x = Error code (See table below):
Error code
1
2
3
4
5
6
7
When the update runs normally, the information LoAd : End is
displayed.
If an error occurs during the control panel update, use the On / Off
button:
1. The control panel restarts (If only the control panel supplies the
programming tool, it starts again too).
2. Switch off the control panel.
Remove the connection cable.
Switch back on.
18
Faults
No communication
The identification mismatch
Loaded program and contents of the flash-memory are not
identical
Problem of status from target's microcontroller
The speed of communication is impossible
Problem to connection between the tool and the target
Control system not compatible (Display for 2 seconds)
The programme contained in the programming tool is not
compatible with the control panel to which it is connected.
Programming tool
Corrections
Check that the control panel is switched on.
Check the connection of the 14-pin connection
cable.
Check that the programme loaded into the tool is
compatible with the control system.
See section 4.6: Check the version of the
downloaded program.
Check that the programme loaded into the tool is
compatible with the control system.
See section 4.6: Check the version of the
downloaded program.
Restart the control panel.
Restart the control panel.
Restart the control panel.
Restart the control panel.
Stop (Stop loading)
Continue (Force loading)
To switch from "Stop" to "Continue" and vice
versa, use keys + or -.
09/12/2014 - 300011650-02

Publicidad

loading