INSTALLATION MANUAL
STAR 500 (23105052-53)
Layout
BAT 1
BAT 2
ADDITIONAL BATTERY
L6
L5
N L
L4
L3
L2
L1
INSTALLATION
1.Remove the lid and fix the flush mounting device by the 4 holes for the fixation of the box. Use siutable wedges.
2. Connect the entrance wire to the terminal board 'IN'
3. Connect the exit wire to the terminal board 'OUT'
4. Insert the fuses
5. Turn the power supply on, than the voltage will supply the device.
6. Wait that the led D2 in SMD on the circuit switches on
7. Connect the batteries inserting them into the space shown in fig.1
Two air-tight lead batteries 12 Volts 7,0 Ah without maintenance. Connect
jumper (fig. 2) for a Total of 24V
PLEASE NOTE: Connect as shown in fig. 2 avoiding casual contacts between the same polarities of one battery.
8. After connecting in series the batteries, wire the cable signed with '+' (coming from the inverter) to the positive terminal board of
the upper battery (BAT 1) and the cable signed with '-' to the negative terminal board of the lower battery (BAT 2).
9.Reclose the lid with the delivered screws.
PLEASE NOTE: Remember that the device must be powered otherwise, after few days the batteries would exhaust and they
would loose working order. In this position batteries can stay workless for 60 days ca.
L6
BATTERY OFF
L5
MINIMUM BATTERY
L4
OVERLOAD
L3
POWER LIMIT
L2
BLACK OUT
L1
ON UPS
Cod. 67410222
4
®
24.5 cm
+
-
24V DC
N L
OUT
IN
FUSE 1=2.5A T
FUSE 2=2.5A T
FUSE 3=32A F
Board 1: MEANING OF SIGNALS
English

TECHNICAL DATA

Loading power
Autonomy with 50% continuous loading
Stand-by autonomy (empty)
Protection degree
Entrance tension
Inverter limit tension
Time from net supplying
UPS switching time
Inverter exit tension
Inverter wave form
Entrance protection fuses
Battery protection fuse
Inverter overloading protection
Rationed battery charger
Complete recharging time
Minimum recharging time
Entrance and exit
Total storage tension
Hermetic lead batteries
Working humidity
Working temperature
Indicating led
PLEASE NOTE: THE INSTALLATION MUST BE CARRIED OUT WITH
DISACTIVATED NET, AND DISCONNECTED BATTERIES AND NETS .
PLEASE NOTE: DO NOT USE WITH CHARGES OVER 500VA.
Exhausted batteries, inverter stops
Last autonomy minute for almost exhausted batteries
Too much power applied, inverter stops
Power applied at maximum, dangerous situation, inverter stops
Defective entrance power tension, inverter working
Device working
REV. 07 - 10/2012
500 va
See board 2
10 hours
IP 65 with SEA plastic box
230V ~ frequency 50H or 115V ~ 60Hz
187V ± 2% / 250 ± 2% ~
Less than 2-3mS
Less than 1 mS
230V ~ ± 5% or 115V± 5% synchronous to the net (PLL)
Sinusoidal, distortion less than 10% ± 0,2%
N2 2,5AT
32 A.FF. (super fast)
Electronic with inner led indication (Board 1)
Stabilized tension with 0,5A limiter
12 hours ca.
2 hours ca.
Screwing terminal board
24V
(Recharging tension 27,6 V
N°2 of 7Ah with input for external supplementary battery
0-90% non condensing
0-40 °C
Operational, emergency, power limit, overloading,
minimum battery, autonomy end.