2

Installation

2.1

Mounting

WARNING!
Electric shock!
Upon opening the housing, live parts are exposed!
Î Always disconnect the controller from power supply
before opening the housing!
The unit must only be located in dry interior rooms.
If the device is not equipped with a mains connection cable and a plug, the device
must additionally be supplied from a double pole switch with contact gap of at
least 3 mm.
Please pay attention to separate routing of sensor cables and mains cables.
In order to mount the device to the wall, carry out the following steps:
1.
Choose a mounting location.
2.
Drill 2 holes (Ø 6 mm, centres 113 mm) and insert the wall plugs.
3.
Fasten the base part of the housing by means of the enclosed screws
(4 x 40 mm, (1)).
Spare fuse
(interior part of cover)
2.2
WARNING!
ATTENTION!
(1)
Do not use the device if it is visibly damaged!
Connecting the device to the power supply must always be the last step of the installation!
Depending on the product version, mains cables and signal cables are already
connected to the device. If that is not the case, please proceed as follows:
Attach flexible cables to the housing with the enclosed strain relief and the cor-
responding screws.
The device is supplied with power via a mains cable. The mains voltage must be
230 V~ (50 Hz).
Connect the signal cable from the controller to the low voltage input of the device:
R In (1 / 2) = double-pole 230-V-control signal cable from the controller

Electrical connection

Electric shock!
Upon opening the housing, live parts are exposed!
Î Always disconnect the controller from power supply
before opening the housing!
ESD damage!
Electrostatic discharge can lead to damage to electronic com-
ponents!
Î Take care to discharge properly before touching the
inside of the device! To do so, touch a grounded sur-
face such as a radiator or tap!
Note:
Strong electromagnetic fields can impair the function of the device.
Î Make sure the device as well as the system are not exposed to
strong electromagnetic fields.
Note:
It must be possible to disconnect the device from the mains at any time.
Î Install the mains plug so that it is accessible at any time.
Î If this is not possible, install a switch that can be accessed.
If the mains cable is damaged, it must be replaced by a special connection
cable which is available from the manufacturer or its customer service.