for IPC 402-8K Insulation Piercing Connector
IPC 402-8
INSTALLING INSULATION PIERCING
CONNECTOR ON CABLE
1) Place the Insulation Piercing Connector on the
insulated cable (see Figure 1).
Insulated
Cable
Figure 1
2. Hold the Piercing Connector in place on the cable
and tighten the setscrew with an insulated wrench
until the screw head shears off (see Figure 2 and 3).
Optional Installation Tool:
Helps installer keep the connector perpendicular to
the conductor while applying torque
(see Figure 2 and 3).
Insulated Cable
Installation Wrench
(Sold separately)
OPTIONAL:
Alignment Tool
Perpendicular with cable,
alternate method
(Sold separately)
Figure 2
Figure 3
TA04672 A
Page 1 of 2
INSTALLATION INSTRUCTIONS
and Neutral Connector Kit
Insulation
Piercing
Connector
OPTIONAL:
Alignment Tool
Parallel with cable,
preferred method
(Sold separately)
Setscrew
Insulation Piercing
Connector
Screw Head
Sheared off
English
INSTALLING CUSTOMER SERVICE CABLE
TO INSULATION PIERCING CONNECTOR
3) Prepare Customer Service Cable by stripping cable to
1 inch (see Figure 4).
4) Install stripped end into one of the cable ports
(Figure 4).
Figure 4
5) Once installed, tighten setscrew on back of connector
to 60 in-lbs. (see Figure 5).
Figure 5
6) For additional Customer Service Cables, repeat
steps 3 - 5 (see Figure 6).
NOTE: Customer Service Cables may enter from either
side of the connector (see Figure 6).
Customer
Service Cable
Figure 6
WARNING
RISK OF SHOCK, DISCONNECT
POWER BEFORE INSTALLATION.
IPC 402-8 N
Cable Port(s)
1"
Customer
Service
Cable
Tighten Setscrew
to 60 in-lbs.
Customer
Service Cables

Publicidad

loading

Resumen de contenidos para ABB Thomas & Betts Blackburn IPC 402-8K

  • Página 1 WARNING RISK OF SHOCK, DISCONNECT POWER BEFORE INSTALLATION. English INSTALLATION INSTRUCTIONS for IPC 402-8K Insulation Piercing Connector and Neutral Connector Kit IPC 402-8 IPC 402-8 N INSTALLING INSULATION PIERCING INSTALLING CUSTOMER SERVICE CABLE CONNECTOR ON CABLE TO INSULATION PIERCING CONNECTOR 1) Place the Insulation Piercing Connector on the 3) Prepare Customer Service Cable by stripping cable to insulated cable (see Figure 1).
  • Página 2 11) Hold the Neutral Connector in place on the cable INSTALLING CONNECTOR COVER OVER and tighten the setscrew with an insulated wrench THE INSULATION PIERCING CONNECTOR until the screw head shears off (see Figure 2 and 3). OPTIONAL Alignment Tool see step 2. 7) Place the Connector Cover (Sold Separately) under the connector and lift up (see Figure 7).
  • Página 3 ADVERTENCIA R IESGO DE ELECTROCUCIÓN. DESCONECTE LA ALIMENTACIÓN ANTES DE LA INSTALACIÓN Español INSTRUCCIONES DE INSTALACIÓN para el Conjunto de Conector perforador de aislamiento y Conector de neutro IPC 402-8K IPC 402-8 IPC 402-8 N INSTALACIÓN DEL CABLE DE SERVICIO DEL CLIENTE NSTALACIÓN DEL CONECTOR PERFORADOR DE AL CONECTOR PERFORADOR DE AISLAMIENTO AISLAMIENTO EN EL CABLE...
  • Página 4 11) Sostenga el conector de neutro y apriete el tornillo INSTALACIÓN DE LA TAPA DEL CONECTOR SOBRE EL de jación con una llave aislada hasta que la cabeza CONECTOR PERFORADOR DE AISLAMIENTO del tornillo se desprenda (vea las Figuras 2 y 3). 7) Coloque la cubierta del conector (se vende por OPCIONAL Herramienta de alineación vea el paso 2.

Este manual también es adecuado para:

Thomas & betts blackburn ipc 402-8Thomas & betts blackburn ipc 402-8 n