Presettable parameters
Standard settings
Expanded settings
Service functions
The following table shows the structure of the PC configuration software
®
ReadWin
2000 interactive menu operation:
• Sensor type
• Connection mode (2-, 3- or 4-wire connection)
• Units (°C/°F)
• Measurement range start (depends on sensor)
• Measurement range end (depends on sensor)
• Coefficient X0 to X4 (on sensor type polynom RTD/TC)
• Temperature compensation (on sensor type polynom TC)
• Cold junction compensation (internal/external on TC connection)
• Temperature external (on TC with cold junction compensation external)
• Compensation resistance (0 to 30  on 2-wire connection
• Fault condition reaction (
• Output (analogue standard/inverse)
• Damping (0 to 100 s)
• Offset (-9.9 to +9.9 K)
• TAG (Measurement point description)
• Identifier (Descriptor)
• Simulation (on/off)
• Reset/factory default
• Serial number (only display)
• Operation code (=release code 281)
®
For detailed ReadWin
documentation contained in the ReadWin
3.6 mA or
21.0 mA; > 21.5 mA is guaranteed)
2000 operating instructions please read the online
®
2000 software.