Descargar Imprimir esta página

Westinghouse W-735 Manual Del Usuario página 3

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTALLATION GUIDE
Removing uorescent lamp system
NOTE: Westinghouse T8 LED is suitable to be installed in T8 standard luminaries.
1. Disconnect power from luminaire.
2. Remove uorescent bulb.
3. Remove wiring compartment cover.
4. Cut all wires which are connected to the ballast and remove from luminaire.
One lamp installation
Retro tting xtures with ONE LAMP
1. Make sure AC power to luminaire is OFF
2. Make sure ground wire from AC supply is securely connected to ground screw inside luminaire
3. Connect black (live) lead wire to lamp holder on one end of luminaire and then connect white (neutral) lead
wire to lamp holder on the opposite end of luminaire. If only one lamp is being installed, proceed to step 4.
Retro tting luminaire with MULTIPLE LAMPS
After completing steps 1-3 above, connect black (live) and white (neutral) lead wires to remaining lamp holders
4. When all connections are complete, place appropriate connectors/wire nuts on the end of any unused wires.
5. Replace wiring compartment cover.
6. Place sticker that is included with this product on wiring compartment cover or other conspicuous place
on or inside of xture. Sticker reads: "This xture has been modi ed. The ballast has been removed. DO
NOT install uorescent lamps in this xture".
7. Install LED tube(s).
8. Re-connect power to luminaire.
Multi lamp installation
Multiple LED Tubes
3

Publicidad

loading