FLUE EXHAUST INSTALLATION
CONCENTRIC FLUE PIPE
Fit the concentric elbow pipe positioning it on the desired direction and insert on it the sealing gasket. Then fit
the appropriate diaphragm (see table below).
Fit the air intake and flue exhaust pipes, observing the distances indicated on the installation scheme. The flue
pipe should slope slightly outward.
100
Max. 3000
DOUBLE FLUE PIPE
Air diaphragm
97
** Air intake Ø 80
ATTENTION: Use only air intake/ fume evacuation kits produced by Lamborghini Caloreclima.
All manuals and user guides at all-guides.com
100
Max. 3000
220
440
CONCENTRIC FLUE PIPE
Max. length
0,5÷1 m
Diaphr.
Ø 87 mm
Maximum length of CONCENTRIC FLUE PIPE 3 m
Maximum length of DOUBLE FLUE PIPE
(Intake + Exhaust) 30 m
Installing an elbow to connect the boiler to the chimney will cause a
drop in pressure.
The values set out in the table below indicate the necessary
modifications to the length of the linear pipes.
TYPE OF INSTALLATION
CONCENTRIC FLUE PIPE
SEPARATE INTAKE/EXHAUST
160
330
DOUBLE FLUE PIPE
Over 1 m
No diaphragm
(hole standard)
ELBOW FITTED
AT 90°
1 m
0,6 m
49
FLUE EXHAUST PIPE
SCARICO
Diaframma
Air diaphragm
aria
No diaphragm
(hole standard)
ELBOW FITTED
AT 45°
0,5 m
0,3 m