UK
14. Use buttons - or + to change parameter settings to
INI.
CZ
15. Select a thermostat.
THERMOSTATS T-166, T-168 AND T-169
DE
15.1 Press and hold the OK button on the
thermostat for about 5 seconds to enter the
settings menu. The settings icon and menu
DK
numbers are displayed in the top right corner
of the display.
15.2 Use buttons - or + (T-169 =
EE
change the numbers to 04 and press OK.
Current control mode is displayed (RT, RFT,
RS or RO).
ES
15.3. Use buttons - or + (T-169 =
change control mode to RO and press OK.
FI
15.4 Use buttons - or + (T-169 =
change the numbers to 09 and press OK. The
text Int YES is displayed, if the thermostat
FR
already is registered as a reference room
thermostat.
HR
15.5. Use buttons - or + (T-169 =
change Int YES to Int CNF.
15.6. The connection indicator starts flashing in
HU
the thermostat display to show that the
registration process begins.
IT
15.7 The current outdoor temperature is shown in
the controller display, and the text Int YES
is shown in the thermostat display when the
LT
registration is complete.
15.8 Press and hold the OK button on the
thermostat for about 5 seconds to exit the
LV
settings menu, or wait about 70 seconds for
the software to exit itself.
NL
THERMOSTAT T-163
15.1 Gently press and hold the registration button
on the thermostat, release when the LED
NO
starts flashing green (located in the hole
above the registration button).
15.2 The current outdoor temperature is shown in
PL
the controller display when the registration
is complete. It might take some time for the
thermostat to send the current temperature
PT
data to the controller. 00.0 is displayed in the
meantime.
RO
16. Press the OK button on the controller to confirm
the change and return to the system parameter
settings.
RU
SE
SK
1 0
Q U I C K G U I D E
or ) to
or ) to
or ) to
or ) to
End registration
N O T E !
If system parameter settings are to be
changed, go to section Setup the system >
Step 3.
17. Use buttons < or > to locate parameter 24 (End)
– Exit system parameter settings.
18. Press the OK button to exit the system parameters
menu.
Setup the system
Change the system parameter settings to setup the
system.
1
2
10 s
3
1 2 3 4 5 6 7
13
14
15
16
17
18
19
20
21
22
23
24
0h
1
4
0h
5
6
24
U P O N O R S M AT R I X M O V E · Q U I C K G U I D E
0h
12
11
10
9
8
7
6
5
4
3
2
1
24
P
AUTO
0h
2
4
6
8
10
12
14
16
18
20
22
24