Technical Data - Trilux LIVELINK LAN DR Instrucciones De Montaje

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 10
EN
Important notes on the status LED
Each DALI channel has its own status LED.
• Status LED glows green: system is booting.
• Status LED glows continuously and flickers occa-
sionally: normal operation (gateway communicating
with devices and server).
• Status LED flickers continuously: high communica-
tion load (e.g. active DALI scan)
• Status LED flashes (approx. every 0.5 s): gateway is
not connected to the server or logged in.
Intended use
Intended for indoor use with a maximum ambient
temperature of: ta 50 °C
Safety class: I
Protection rating: IP20
Disposal of waste electrical and electronic equipment
Always collect and dispose of old electrical
and electronic equipment separately at the
end of its service life. In case of doubt, seek
information about environmentally-compliant waste
disposal from your local district authority or special
waste disposal companies. Current information on the
energy efficiency class of the selected product version
can be found in the corresponding data sheet for the
luminaire. Instructions for replacing or removing the
light source in accordance with Regulation 2019/2020/
EU can be found at:
www.trilux.com/EcoDesign
Directive 2014/53/EU
Simplified EU Declaration of Conformity according
to the RED Directive if the luminaire is equipped
with a control gear unit with NFC interface or a radio
component:
TRILUX hereby declares that the following radio sys-
tem type complies with Directive 2014/53/EU:
...
LIVELINK
The full text of the EU Declaration of Conformity is
available on the Internet at:
www.trilux.com/eu-conformity
8 | 36
10258341 | 211217 | © trilux.com
LIVELINK LAN DR
LIVELINK LAN DR

TECHNICAL DATA

LiveLink LAN...
Input voltage
Input current (nominal)
Input frequency
Standby power
consumption
DALI current
DALI devices
(stand-alone operation)
DALI groups
(stand-alone operation)
DALI cable length
L cable length
Number of light scenes
(stand-alone operation)
Number of radio
modules
ZigBee
ZigBee range
Service life
Standards
© trilux.com | 211217 |10258341
EN
... DR
... DR+RC
... DR Connect
220-240 VAC
70 mA
50 / 60 Hz
N/A
180 mA
max. 64
max. 16
max. 300 m
max. 25 m
max. 50
---
max. 50
---
IEEE 802.15.4
max. 30 m (in
---
open field)
50,000 h
EN 301489-1
---
EN 301489-17
EN 300328
EN 61347-2-11
EN 62386-101
EN 62386-103
EN 55024
EN 55032
9 | 36

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Livelink lan dr+rcLivelink lan dr connect

Tabla de contenido