CLASS 2
1
24 VAC
2
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
–
+
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING IF AVAILABLE.
Fig. 14. Wiring for modulating (0/2-10 VDC)
proportioning control, MS75 (shown) and MS71.
CLASS 2
1
24 VAC
2
4 TO 20 mA
490 TO 510
PROPORTIONING
OHMS,
CONTROLLER
1/2 W
MINIMUM
–
+
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING IF AVAILABLE.
Fig. 15. Wiring for 4-20 mA proportioning controllers,
MS75 (shown) and MS71.
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
ACTUATOR
1
RED
V
2
BLACK
3
WHITE
0°-90°/MODULATING
4
BROWN
90°-0°/FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
, FWD
FLOATING
, REV
FLOATING
M37320
ACTUATOR
RED
1
V
2
BLACK
WHITE
3
0°-90°/MODULATING
4
BROWN
90°-0°/FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
FLOATING, FWD
FLOATING, REV
M37321
7
CLASS 2
1
24 VAC
2
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
–
+
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION
AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING
IF AVAILABLE.
Fig. 16. Wiring for modulating (0/2-10 VDC)
proportioning control operating multiple actuators,
MS75 (shown) and MS71.
CLASS 2
24 VAC
CONTROLLER
HOT
COM
S-BUS
S-BUS
LINE VOLTAGE POWER SUPPLY.
1
PROVIDE DISCONNECT MEANS
AND OVERLOAD
PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
ADDRESS SELECTOR
Fig. 17. Wiring for SYLK BUS control, MS3103.
ACTUATOR
1
RED
V
2
BLACK
3
WHITE
0°-90°/MODULATING
4
BROWN
90°-0°/FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
, FWD
FLOATING
, REV
FLOATING
ACTUATOR
RED
1
V
2
BLACK
3
WHITE
0°-90°/MODULATING
4
90°-0°/FEEDBACK
BROWN
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
, FWD
FLOATING
, REV
FLOATING
M37322
ACTUATOR
RED
BLACK
BROWN
S-BUS
BROWN
S-BUS
ADDRESS 11
ADDRESS 12
ADDRESS 13
ADDRESS 14
ADDRESS 15
TEST
31-00141M—06