5.4
Testing the Detector
1.
Test the detector at the point of time you feel the lamp needs to
be switched on.
2.
Turn the SENS and LUX knobs fully clockwise; turn the TIME
knob fully anti-clockwise.
3.
Switch on the power. The detector needs a warm-up time of
± 30 seconds before it will switch on the connected lamp. When
no signal is detected, the lamp will switch off after
± 10 seconds.
4.
Turn the LUX knob fully anti-clockwise. The lamp should switch
off.
5.5
Setting the Detector
1.
Turn the SENS and LUX knobs until the lamp switches on.
2.
Now, set the switch-off delay with the TIME knob going from
± 10 seconds to ± 7 minutes.
3.
Close the detector with the cover and tighten the screw.
V. 02 – 15/10/2015
PIR1300
5
©Velleman nv